4.6 Optional fuel tank installation
For Diesel-fuel powered generating sets, you
can connect two lines (delivery and return) di-
rectly to the tank by means of fuel pipes hav-
ing an inside diameter of 7 mm.
The fuel tank must be located so the fuel hose is
as short as possible. Ensure that nor must the
cross-section of the hose be diminished by
squeezing, bending. We also suggest you install
the tank at the same height as the generating
set; if you do place it at a lower position, there
must never be more than 20 cm level difference .
Never place the fuel tank near heat sources; pro-
tect it from any outside infiltration of water.
To connect the tank to the generating set, use a
flexible hose suitable for green petrol, having an
inside diameter of 5 mm (petrol sets)(part.
no.05426)
Filling the fuel tank should be via a 50 mm ID
pipe or house(pat. no. 05425), suitable for green
petrol (fig.10 ref. 2)
4.7 Fuel reserve
The tank is provided with an electrical reserve.
To connect use a suitable electrical cable to join
tank and generator set. (fig. 10 ref. 1 to fig. 6 ref.
4) Cable not supplied.
The fuel tank (code 05421) has reserve of about
4 litres.
The warning light on the control panel (Fig. 11
ref. 1) will light up to indicate when the fuel level
inside the tank has gone below the reserve level.