50
4.2.8 CM relay contacts operation
Relay contacts of CM_16_1 change their state as described below.
Table 12 - CM relay Ready contacts operation
CM state
Relay Ready contacts state
NO
NC
CM is ready for close or open operation
Open
Closed
CM is not ready for close or open operation
Closed
Open
Table 13 - CM relay “ISM main contact position“ contacts operation
ISM state
Relay
“
ISM main contact position“ contacts state
NO
NC
ISM is closed
Open
Closed
ISM is open
Closed
Open
Table 14 - CM relay Malfunction contacts operation
CM state
Relay Malfunction contacts state
NO
NC
Power supply voltage is absent for more than 1.5
seconds (1 blink of LED Malfunction)
Closed
Open
Exessive trip or close time (2 blinks of LED Malfunc-
tion)
Open
Closed
Actuator coil isolated (3 blinks of LED Malfunction)
Open
Closed
Short circuit of Actuator coil (4 blinks of LED Mal-
function)
Open
Closed
Manual Trip and Lock (5 blinks of LED Malfunction)
Closed
Open
Overheat (6 blinks of LED Malfunction)
Closed
Open
State of ISM is not defined (7 blinks of LED Malfunc-
tion)
Open
Closed
Internal fault of CM (continuous light of LED Mal-
function)
Open
Closed
5. Commissioning
Summary of Contents for TAVRIDA ELECTRIC VCB15 LD
Page 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Page 3: ...1 Product description...
Page 7: ...2 Nameplates and seals...
Page 11: ...3 Product handling...
Page 23: ...4 Installation...
Page 50: ...5 Commissioning...
Page 57: ...6 Operation...
Page 61: ...7 Maintenance and troubleshooting...
Page 66: ...8 Disposal...
Page 68: ...Appendix 1 Product range...
Page 71: ...Appendix 2 Overall drawings...
Page 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Page 85: ...Appendix 3 Secondary schemes...
Page 86: ...87...
Page 87: ...88...
Page 88: ...89...
Page 89: ...90...
Page 90: ...91...
Page 91: ...92...
Page 92: ...93...