Even after the CM is disconnected from all the power supplies there still may be hazardous voltage on the CM
connectors. Achievement of safe voltage level is indicated by the extinction of all LEDs on the CM front panel.
This may take up to 15 minutes after the CM is deenergized.
b) HD ISM
a) LD ISM
Figure 77
Sample of earthed cable shielding on ISM side
Type of MCB shall be selected according to CM consumption data given in Table 1.
If the CM is connected to DC voltage, pay special attention to the correct polarity for CM_16_1(60_Par2_Par3) .
Figure 78
CM_16 power supply connection
Power supply inputs
~ (+) ~ (-)
MCB
Connection of CM_16_1 to power supply is shown below.
If Manual generators CBunit_ManGen are used for charging the CM, DC voltage outputs shall be connected to
power supply inputs of CM_16_1. Pay special attention to the correct polarity for CM_16_1(60_Par2_Par3).
Arrangement of output wires of Manual generators CBunit_ManGen_1 and CBunit_ManGen_2:
• red colour wire - positive polarity output wire;
• black colour wire - negative polarity output wire;
• yellow-green clour wire - manual generator earting wire.
4.2.6 Auxiliary supply
Summary of Contents for TAVRIDA ELECTRIC VCB15 LD
Page 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Page 3: ...1 Product description...
Page 7: ...2 Nameplates and seals...
Page 11: ...3 Product handling...
Page 23: ...4 Installation...
Page 50: ...5 Commissioning...
Page 57: ...6 Operation...
Page 61: ...7 Maintenance and troubleshooting...
Page 66: ...8 Disposal...
Page 68: ...Appendix 1 Product range...
Page 71: ...Appendix 2 Overall drawings...
Page 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Page 85: ...Appendix 3 Secondary schemes...
Page 86: ...87...
Page 87: ...88...
Page 88: ...89...
Page 89: ...90...
Page 90: ...91...
Page 91: ...92...
Page 92: ...93...