4.2.3 CM secondary connections
Figure 71
Terminal arrangement of the the CM
CM_16_1 has secondary connectors as shown below.
X1
X3
Terminal No.
Connection
Terminal No.
Connection
1
Power supply input (+)
1
Actuator coil output
2
Power supply input (-)
2
Actuator coil output
3
Relay output 1 NO
4
Relay output 1 Com
5
Relay output 1 NC
6
Relay output 2 NO
7
Relay output 2 Com
8
Relay output 2 NC
9
Relay output 3 NO
10
Relay output 3 Com
11
Relay output 3 NC
12
Close input
13
Close input
14
Trip input
15
Trip input
Table 10 - CM terminal arrangement
CM relay functionality:
• Relay 1 - “ISM main contact position” relay;
• Relay 2 - “Ready” relay;
• Relay 3 - “Malfunction” relay.
Relay “ISM main contact position“ keeps its state after CM power supply disconnection.
Summary of Contents for TAVRIDA ELECTRIC VCB15 LD
Page 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Page 3: ...1 Product description...
Page 7: ...2 Nameplates and seals...
Page 11: ...3 Product handling...
Page 23: ...4 Installation...
Page 50: ...5 Commissioning...
Page 57: ...6 Operation...
Page 61: ...7 Maintenance and troubleshooting...
Page 66: ...8 Disposal...
Page 68: ...Appendix 1 Product range...
Page 71: ...Appendix 2 Overall drawings...
Page 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Page 85: ...Appendix 3 Secondary schemes...
Page 86: ...87...
Page 87: ...88...
Page 88: ...89...
Page 89: ...90...
Page 90: ...91...
Page 91: ...92...
Page 92: ...93...