59
6.1 Switching
6.1.1 Closing
To close the ISM main contacts the CM close command shall be applied. It is a “dry contact“ input so no external
voltage should be applied.
The Close command will be accepted if:
• CM state is “Ready” (Ready LED flashes green);
• no Trip command is applied;
• optional electrical interlock is unlocked;
• mechanical and electrical interlock is unlocked (in case of ISM15_Shell_2 only).
If Close command is applied and held before the CM is in a “Ready“ state the Close command will not be
accepted. If auxiliary power is not available, the manual generator CBunit_ManGen shall be used to charge the
CM capacitors and to close the ISM. Mechanical closing is not possible.
1. Close command input
2. Trip command input
1
2
Figure 82
CM_16 close and trip inputs
If Manual generators CBunit_ManGen are used to charge the CM, the Manual generator handle shall be rotated
until the Ready LED of the CM flashes green (approximately 30 seconds). Then the ISM close command can be
applied to the CM. One possible variant is the connection of NO and Common contacts of relay Ready to the
Close command input of the CM. Be aware that in this case the ISM will be closed automatically once the CM
reaches the Ready state.
If Manual generators CBunit_ManGen are used for charging the CM, DC voltage outputs of the Manual
generator shall be connected to the power supply inputs (Figure 83) of CM_16_1. Pay special attention to the
correct polarity for CM_16_1(60_Par2_Par3).
Figure 83
CM_16 power supply connection
Power supply inputs
~ (+) ~ (-)
MCB
Summary of Contents for TAVRIDA ELECTRIC VCB15 LD
Page 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Page 3: ...1 Product description...
Page 7: ...2 Nameplates and seals...
Page 11: ...3 Product handling...
Page 23: ...4 Installation...
Page 50: ...5 Commissioning...
Page 57: ...6 Operation...
Page 61: ...7 Maintenance and troubleshooting...
Page 66: ...8 Disposal...
Page 68: ...Appendix 1 Product range...
Page 71: ...Appendix 2 Overall drawings...
Page 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Page 85: ...Appendix 3 Secondary schemes...
Page 86: ...87...
Page 87: ...88...
Page 88: ...89...
Page 89: ...90...
Page 90: ...91...
Page 91: ...92...
Page 92: ...93...