Maintenance
—Type
502A
Low frequency distortion
is usually caused by a change
in
the
time constant of the input coupling circuit. If
tubes
become
gassy,
their resultant grid current
will
establish a
time constant
network which will affect
the low frequency
response
of the circuit.
High
frequency response can be affected considerably by
an
improperly adjusted probe. Consequently, in
any case of
high
frequency distortion you should first check the probe
adjustment. Refer
to
the Operating Instructions for the
compensation
procedure. Other factors
which can affect the
high
frequency response of the vertical amplifier
are mainly
related
to the high freqeuency compensation networks.
An
overshoot waveform shown accentuated in Fig. 4-11 is
the
result of excessive
high frequency compensation. This
can
be caused by a tube condition known as cathode inter
face. If
this type of distortion is detected, you should check
the
tubes in the amplifier. If tube replacement does not
completely
correct the trouble, you
should then check the ad
justment
and
operation of the high frequency compensation
circuits.
For improper triggering
Improper
triggering
can be caused by a defective trigger
pickoff circuit.
The trouble may be caused either by a faulty
cathode
follower, V493 or by a defective component in the
circuit.
TROUBLESHOOTING
THE TIME-BASE TRIGGER
If
the trouble occurs in some but not all positions of the
TRIGGER SELECTOR
switch,
the
trouble
is
likely due
to
a
defective
TRIGGER
SELECTOR
switch or input coupling circuit.
If
the
trouble
occurs in all positions of the TRIGGER
SELECTOR
switch,
either
the trigger input
amplifier
or the
trigger
multivitbrator
will be at fault. You should check
tubes
V24 and
V45.
NOTE
All
voltages in this section are measured with a
20,000
ohms-per-volt voltmeter.
To
determine which stage is defective, rotate the TRIG
GERING LEVEL
Control fully counter-clockwise to the
AUTOMATIC
position. With no triggering signal, the sweep
should
apear
on
the crt. If the
sweep does not appear,
the
trigger multivibrator is defective. If the sweep does
appear,
either the trigger input amplifier or the trigger
multivibrator
may be at fault.
A
check on the trigger input amplifier
circuit may be
made as
follows:
With the TRIGGERING LEVEL Control still
in
the AUTOMATIC position,
measure the voltage at the
plate,
pin 6,
of V24B. This voltage should be approximately
+
96
volts. If the voltage is incorrect, the trigger input am
plifier
circuit
is defective. The trouble will probably exist
in the resistors
or
switches of the circuit.
If
the voltage measured is correct, rotate the TRIGGER
ING LEVEL
Control
completely through its range while
monitoring
the voltage at
pin 6 of V24B. The voltage should
vary
between approximately 34
and 135 volts. An incorrect
voltage range
indicates a defective trigger
input amplifier or
TRIGGERING
LEVEL Control.
If
the voltage range is correct,
the trouble will
be in the trigger multivibrator.
A trouble
in
the multivibrator will probably be due to defective re
sistors.
The voltage divider
network between the plate of
V45A
and the grid of V45B is particularly critical.
TROUBLESHOOTING
THE TIME-BASE
GENERATOR
For
free-running operation
If
the Time-Base Generator free runs when the TRIGGER
ING
LEVEL Control is
not in the RECURRENT or AUTOMATIC
positions
this is due to astable operation of the sweep gating
multivibrator. This trouble
will probably be due to defective
resistors
in the grid circuit of V135A (resistors R185, R186,
or
R111) or in the
grid
circuit of V145A (resistors R141 or
R143).
For no
horizontal sweep
If
the Time-Base
Generator is not producing a sawtooth
waveform
when
the TRIGGERING LEVEL
Control is in the
RECURRENT position, some defect in the circuit
is causing the
output
to remain at some fixed voltage. A clue to the cause
of
this trouble
can be obtained by measuring the plate volt
age
of the Miller tube, V161A. The voltage reading obtained
will
probably be either approxi300 volts or approxi
30
volts. A reading of +300 volts indicates that
the
Miller stage
has run
up
and has not been reset, while a
reading
of +30 volts indicates
that the Miller stage is not
being
allowed to runup. The condition that actually exists
will depend
on the type of trouble occurring in the circuit.
The
two conditions
of plate voltage will be handled sepa
rately
in the
following paragraphs.
Miller
Stage is Run-up
If
the voltage at the plate of the Miller tube, V161A,
is
high,
the
tube is cutoff. This can result from any one
of
the
following conditions: (1) Disconnect Diodes do not
conduct,
(2)
Sweep-Gating Multivibrator does not reset,
(3) Hold-Off
Cathode Followers do
not reset the Sweep-
Gating
Multivibrator and
(4) Runup Cathode Follower does
not drive the
Hold-Off Cathode Follower. The defective stage
can
be detected by a
series of systematic voltage measure
ments. When
an improper voltage reading
is obtained, this
will
indicate the defective stage.
Check
the votage at the grid of the Miller tube. If
the
reading
is
only a few volts negative,
the Disconnect Diodes
are
probably conducting normally and can
be eliminated as
a
possible cause
of the trouble. If the voltage is more nega
tive
than —50 volts, however, the diodes are not conducting.
Check
V152
and resistors R147 and R148.
Measure
the voltage at
the output of the Time-Base Gener
ator
(pin 3 of V161 B). If this voltage is approxi250
volts, the Runup
Cathode Follower stage
may be assumed
to be operating correctly.
If this voltage is low, however,
the
stage
is defective and
its grid and cathode circuits should
be
checked.
4-7
Summary of Contents for 502A
Page 4: ......
Page 22: ...Circuit Description Type 502A Fig 3 2 Simplified Sweep Trigger Circuit t i CO ...
Page 27: ...Circuit Description Type 502A Fig 3 4 Simplified Horizontal Amplifier 3 9 ...
Page 32: ...Circuit Description Type 5O2A Fig 3 7 Simplified Calibrator Circuit 3 14 ...
Page 34: ...NOTES ...
Page 56: ...NOTES ...
Page 60: ...Parts List Type 502A LEFT SIDE 6 4 ...
Page 64: ...Parts List Type 502A RIGHT SIDE 6 8 ...
Page 67: ...Parts List Type 502A TOP 6 11 ...
Page 70: ...Parts List Type 502A BOTTOM 6 14 ...
Page 73: ...Parts List Type 502A REAR 6 17 ...
Page 89: ...TYPE 502A OSCILLOSCOPE A ...
Page 90: ...A BLOCK DIAGRAM MRH Z6 3 ...
Page 91: ... TYPE 502A OSCILLOSCOPE A ...
Page 92: ...A CIRCUIT NUMBERS 1 THRU 59 I Ixj 263 TIME BASE TR IGGER ...
Page 93: ......
Page 95: ...TI M I NG RESI 5TORS TIMING CAPACITORS TYPE 502A OSCILLOSCOPE ...
Page 96: ...SWI6O HOLD OFF CAPACITORS 4 RESISTORS TIM ING CAPACITORS o A TIMING SWITCH job ...
Page 98: ... 1 INPUT AMPLIFIER OUTPUT AMPLIFIER A CIR CUIT NUMSER 5 300 THR U 399 ZG3 joe ...
Page 100: ...CMO 363 VERTICAL ATTENUATOR SWITCH A ...
Page 103: ...TYPE 5O2A OSCILLOSCOPE OOM HEATER WIRING DIAGRAM ...
Page 104: ...POWER SUPPLY CIRCUIT NUMBERSI 600 THRU 799 ...
Page 106: ...CIR CUIT NUMBER S 800 THR U 869 CRT CIRCUIT c 9G4 ...
Page 107: ...CA LIBp A TOp MULTIVIBP A TOR 1 IOOV o TYPE 5O2A OSCILLOSCOPE A ...
Page 108: ...CAL OUT CF CALIBRATOR A CIRCUIT NUMBERS 8 7O THRU 899 4Z ...