Note that
Contact 1
will appear as
Aux Input 1A
or
Aux Input 2A
in the Config Tool software depend-
ing on the function selected.
Contact 2
will appear as
Aux Input 1B
or
Aux Input 2B.
Aux inputs are
non-latching by default but can be configured to be latching within the LS450 Config Tool Software.
The PM123 may also be used as a check in device. If a normally open dry contact is connected to
Contact 1
, and the contact is closed at any point during the check in window, the check in requirement
will be satisfied. If a device such as a motion detector or pressure pad is used for check in, connect the
output from the device to
Contact 1
.
If a normally open dry contact is connected to
Contact 2
and changes state at any point during the
check in window, the check in requirement will be satisfied. This is useful if a door contact switch is to
be used for check in. In this instance, if the switch is closed at the start of the check in period, opening
the switch at any point during the check in period will satisfy the check in requirement.
For more information about check in, see
Check In on page 30
.
Connect NC415AV Master Stations
The two 8P8C jacks on the right side of the NC120 CE Module
are the connections for the NC415AV Master Stations. Each jack
supports three NC415AV Master Stations with no more than
1,000 feet of CAT5 or better cabling on the run. Wire the 8P8C
connectors for the NC415AV Master Stations according to the
T568B standard.
To connect more than one NC415AV Master Station to each
port, use a CT400P5 splitter at any point along the master station
cabling run.
Figure 10 - T568B Standard Wiring
Much like room controllers, each NC415AV Master Station must also be assigned a unique address (
0
,
1
, or
2
) using the DIP switch on the rear of the master. The NC120 CE Module will automatically assign
a master name (e.g., 01M1) to each master. This name can be changed in the LS450 Config Tool soft-
ware.
Figure 11 - NC415AV Master Station Connections
Copyright
©
TekTone Sound and Signal Mfg., Inc. All Rights Reserved
IL992 Tek-CARE120 Installation Manual
|
19
Installation