Configuration Setup
Configure an Autodetect Configuration
Before beginning system programming, perform a complete test of the system. Ensure that calls annun-
ciate at the expected LI122-Series Room Controllers and that call type annunciation from SF123 2-But-
ton Pull-Cord stations are correct.
Start the LS450 Config Tool software. On the splash screen, choose the IP address of the Tek-CARE120
system on the left and select
Load Configuration from System
on the right. The default configuration
will be loaded into the LS450 Config Tool software.
Figure 18 - Config Tool Splash Screen
Next, choose
File>Save Configuration As
, choose a descriptive file name, and save the configuration.
Enabling and Naming Modules
Navigate to the
Modules
page. In the
Modules
list, verify that all of the installed NC120 CE Modules
installed on your system are marked as existing.
Note that the Number in the Modules list corresponds to the DIP switch address of the CE modules.
If desired, add
Location
for the module. To add a location for a module, select a module from the list
and click the
Edit
button to unlock the
Details
pane for editing. Type a location into the
Location
field,
and click the
Apply
button.
Repeat this process for each module installed on the Tek-CARE120 system. If a Tek-CARE server is
installed, scroll to the bottom of the
Modules
list and enable the NC475 Module.
26
|
IL992 Tek-CARE120 Installation Manual