Ensure that both the Red/Blue and White domes are marked as
Exists.
Select
LI122_R
if the room con-
troller has red LEDs or LI122_B if the room controller has blue LEDs. If the station must be set up as a
duty station or a zone light, change the behavior of the red/blue and white domes to Red or Blue Zone
Dome and White Zone Dome respectively.
This will enable the Station ID to watch zones on the system and annunciate a call when needed.
The
Single Bed
,
Dual Bed
, and
Duty/Zone
buttons at the bottom of the
Edit Multiple
window can be
used to quickly set up the default station connection points.
Ensure that the
Virtual Station Exists
box is checked. This will automatically enable the Station ID
selected and simplify future editing.
Once all selections have been made, click the
Apply
button. Repeat the edit multiple process for all wir-
ing configurations.
For information on room level reset, check in, editing stations, zoning stations, and disabling points refer
back to
Configure an Autodetect Configuration on page 26
.
Secondary Dome Annunciation
If desired, calls from one station may be forced to annunciate on the dome light of another station. The
dome light set up as the secondary annunciator must be on the same module as the primary annunciator.
To choose a dome light to serve as a secondary annunciator, navigate to the primary station in the
Sta-
tions
page. Select the desired secondary dome annunciation station from the drop-down menu.
Repeat for all remaining stations requiring secondary dome annunciations.
Move Points to Stations
Occasionally, it may be necessary to assign a point to a different station than it is defaulted to. To move
points between Station IDs, select the point to be moved from the points list, then click the
Edit
button.
From the assigned Station menu, select the Station ID and click the
Apply
button.
Editing Hardware Behaviors
By default, the Tek-CARE120 system generates Routine calls from SF121s and SF122s, and Code, Bath,
Emergency, and Emergency 2 calls from SF123s, depending on the function selected in the points list.
PM123s will generate Aux Input 1 or Aux Input 2 calls by default.
To change the type of call generated, select
Behaviors
in the page selection pane of the Config Tool.
Click the
Edit
button in the
Details
pane to unlock it for editing.
The call types generated by various inputs on the system can be edited on the hardware page shown in
Figure 22 on page 34
.
Escalation
may also be set for SF121s and SF122s.
For PM123s, note that Aux Input 1 and Aux Input 2 calls follow the position of the monitored switch.
When the normally open switch is closed, the selected call is placed, and when the switch opens again,
the call automatically clears.
To program a PM123 with latching calls that must be acknowledged from a master station, use the selec-
tions for Aux Input 1A/1B Acknowledged. This will trigger a call when the switch closes, and the call
will remain latched in the system until it is acknowledged, regardless of the position of the switch.
Note that any changes made to the
Virtual Station Default
behavior are global.
Click
Apply
once all edits are made.