1592006207 XB570L GB r1.1 26.08.2015
XB570L
11
rrd Regulation restart with door open alarm: Y
=count down and regualtion restart when door open alarm
is signalled;
n
=compressor and fans stay according to the
odC
parameter when door open alarm is
signalled.
d2F Second digital input configuration (26-27):
(EAL; bAL)
EAL
=external alarm;
bAL
=serious alarm,
regulation is stopped.;
d2P: Configurable digital input polarity (26-27):
(OP; CL) select if the digital input is activated by opening
or closing the contact.
OP
=opening;
CL
=closing.
did Time delay for digital input alarm:
(0 to 255 min) if
d2F=EAL
or
bAL
(external alarms),
did
parameter
defines the time delay between the detection and the successive signalling of the alarm.
AUXILIARY RELAY CONFIGURATION
oA1 First auxiliary relay configuration (7-8):
ALL
=alarm;
Lig
=light;
AuS
=second thermostat;
tMr
=auxiliary relay enabled by keyboard;
C2
=second compressor: it is always switched on during the Cycles while depends on the 2CH
parameter during the holding phase.
oA2 First auxiliary relay configuration (1-2):
ALL
=alarm;
Lig
=light;
AuS
=second thermostat;
tMr
=auxiliary relay enabled by keyboard;
C2
=second compressor it is always switched on during the Cycles while depends on the 2CH
parameter during the holding phase.
oA3 First auxiliary relay configuration (9-10)
ALL
=alarm;
Lig
=light;
AuS
=second thermostat;
tMr
=auxiliary relay enabled by keyboard;
C2
=second compressor: it is always switched on during the Cycles while depends on the 2CH
parameter during the holding phase.
SECOND RELAY MANAGEMENT
2CH Compressors setting during the holding phase (used only if one OAi =C2):
The second compressor is always switched on during the phases, during the holding depends on this
parameter.
The
2CH
sets which compressor is used during the holding phase.
Second compressor operates on
SET+OAS
. (SET is the value loaded during the holding phase of each
cycle). It starts oAt min after the first compressor.
The following table shows how it works:
Holding
2CH =C1
C1 on
2CH =C2
C2 on
2CH =1C2
C1 on; C2 On
OAt Second compressor switching on delay:
(0 to 255 min) time delay between the switching on of the
first and second compressor.
OAS Set point for second compressor
(-50 to 50, res.1°C or 1°F) this set point is a differential add to the
set point of the first compressor.
ES:
OAS=0
the set point of the second compressor s the same set point of the first compressor.
OAS=5
the set point of the second compressor is SET (of first compressor) + 5;
OAS=-5
the set point of the second compressor is SET (of first compressor) – 5.
OAH Differential for second compressor:
(-12.0 to 12.0, res.0.1°C or 1°F, always
≠
0) second compressor
cut IN is SETH+OAS+OAH. Second compressor cut out is when the temperature SETH+OAS.
OAi Probe selection for the second compressor: rP
=thermostat probe;
EP
=evaporator probe;
tiM
=cycle
count down;
i1P
=insert probe 1;
i2P
=insert probe 2;
i3P
=insert probe 3.
OSt AUX output timer:
(0 to 255 min) time in which the AUX output stays ON. It is used when
oA1
or
oA2
or
oA3=tMr
. With
oAt=0
the AUX relay is switched on and off only manually.
OSS Set point for AUX output, used when oA1 or oA2 or oA3=AUS:
(-50 to 50, res.1°C or 1°F).
OSH Differential for AUX output:
(-12.0 to 12.0, res. 0.1°C or 1°F, always
≠
0) intervention differential for the
set point of the AUX output, with OAH<0 the action is for heating, with OAH>0 it is for cooling.
COOLING (OSH>0):
AUX output cut IN is
OSS+OAH
. Second compressor cut out is when the
temperature
SETH+OAS
.
AUXILIARY RELAY MANAGEMENT
Summary of Contents for BLC10
Page 1: ...BLAST CHILLER FREEZER User Manual PT SL 49 61 EN FR IT ES 3 13 25 37...
Page 2: ...2...
Page 9: ...9 QUICK GUIDE For the daily use...
Page 13: ...REFROIDISSEURS CONG LATEURS RAPIDES Manuel d utilisation PT SL 49 61 FR IT ES 13 25 37...
Page 14: ...14...
Page 21: ...21 GUIDE RAPIDE Guide rapide quotidien...
Page 25: ...ABBATTITORI CONGELATORI Manuale d uso PT SL 49 61 IT ES 25 37...
Page 26: ...26...
Page 33: ...33 33 GUIDA RAPIDA Guida pratica quotidiana...
Page 37: ...ABATIDORES CONGELADORES Manual del usuario PT SL 49 61 ES 37...
Page 38: ...38...
Page 45: ...45 GU A R PIDA Gu a r pida diaria...
Page 49: ...PT SL 49 61 ABATEDORES DE TEMPERATURA CONGELADORES Manual do utilizador...
Page 50: ...50...
Page 57: ...57 GUIA R PIDO Guia r pido di rio...
Page 61: ...SL 61 HLADILNIK ZAMRZOVALNIKA ZA HITRO HLAJENJE ZAMRZOVANJE Navodila za uporabo...
Page 62: ...62...
Page 69: ...69 HITRI VODNIK Za dnevno uporabo...
Page 73: ...1592006207 XB570L GB r1 1 26 08 2015 XB570L 2 20 XB590L XB570L...
Page 94: ...1593006207 XB570L FR r1 0 26 08 2015 XB570L 2 24 XB590L XB570L...
Page 118: ...1591006207 XB570L IT r1 1 26 08 2015 XB570L 2 24 XB590L XB570L...
Page 141: ...1591006207 XB570L IT r1 1 26 08 2015 XB570L 25 24...
Page 142: ...1594006207 XB570L SP r1 0 26 08 2015 XB570L 2 20 XB590L XB570L...
Page 162: ...XB590L XB570L...
Page 177: ...1592006207 XB570L GB r1 1 26 08 2015 XB570L 16 20 3 12 2 MONTAGEM...
Page 184: ...1592006207 XB570L GB r1 1 26 08 2015 XB570L 2 20 XB590L XB570L...