(C) Auto_Run Mode for Single Cycle
The speed of final step will be held to run.
For example :
Sn-44
=
3
Sn-45~48 = 1 (FWD) Sn-49~60
=
0
An-01
∼
16, Bn-21
∼
36
:
same setting as the example (A)
15 Hz
30 Hz
50 Hz
Freq.
An-01
An-02
An-03
An-04 (20Hz)
20s
25s
30s
40s
(Bn-21) (Bn-22)
(Bn-23)
(Bn-24)
•
Sn-44 = 1~3 : If the inverter stops and re-starts again, it will continue running from
the unfinished step, according to the setting of Sn-44.
= 4~6 : If the inverter stops and re-starts again, it will begin a new cycle and
continue running according to the setting of Sn-44.
Sn-44
1~3
4~6
Output Frequency
time
Output
Frequency
Run
Command
Continue running from
unfinished step
stop
run
run
time
Output
Frequency
Run
Command
begin a new cycle
stop
run
run
•
ACC/DEC time follow the setting of Bn-01
,
Bn-02 in Auto_Run Mode.
•
If the setting values of Bn-21
∼
Bn-36 are all zero, the Auto_Run Mode is disabled.
(46) Applied Torque Load (Sn-61)
•
Select either the constant torque load (Sn-61=0) or varied torque load (Sn-61=1).
The inverter will automatically choose the proper V/F pattern and change the
inverter overload protection curve. (See page 69 for ‘INVERTER CAPACITY
SELECTION’).