95
(40) PG Speed Control Settings (Sn-40)
Sn-40 = 0 : Disable speed control function.
= 1 : Enable speed control.
= 2 : Enable speed control. No integral action during ACC/DEC.
= 3 : Enable speed control. Integral action is enabled.
(41) Operation Selection at PG Opens (Sn-41)
Sn-41 = 0 : deceleration to stop (Bn-02)
= 1 : coast to stop
= 2 : deceleration to stop (Bn-04)
= 3 : continue to run
}
Display “PG Open
”
alarm.
Blinking display “PG Open” alarm.
(42) Operation Selection at PG Speed Deviation Over (Sn-42)
Sn-42 = 0 : deceleration to stop (Bn-02)
= 1 : coast to stop
= 2 : deceleration to stop (Bn-04)
= 3 : continue to run
}
Display ”Sp. Deviat Over” fault message.
Blinking display “Sp. Deviat Over” alarm.
(43)
Overspeed Detection (Sn-43)
Sn-43 = 0 : deceleration to stop (Bn-02)
= 1 : coast to stop
= 2 : deceleration to stop (Bn-04)
= 3 : continue to run
}
Display ”Over Speed” fault message.
Blinking display “Over Speed” alarm.