75
(10) Frequency Command Characteristics Selection
(Sn-10)
Sn-10 = 0 : Forward characteristics of frequency command
(0~10V or 4~20mA /0~100%)
= 1 : Reverse characteristics of frequency command
(10~0V or 20~4mA /100~0%)
(11) Scan Time at Input Terminal
(Sn-11)
•
Setting of scan frequency of input terminal (Forward/Reverse, multi-function
input)
Sn-11 = 0 : Scan input terminals every 5ms.
= 1 : Scan input terminals every 10ms.
(12) Overtorque Detection Selection
(Sn-12)
•
When overtorque detection is enabled, be sure to set the value of the overtorque
detection level (Cn-32) and the overtorque detection time (Cn-33). An overtorque
condition us detected when the current exceeds the overtorque detection level for
longer than the overtorque detection time.
Sn-12
Function
Display
0
Overtorque detection disabled
1
Detect only during speed agree. Continue operation after detection.
(Miner fault)
“Over Torque” blinks
2
Detect only during speed agree. Stop output after detection (Fault)
“Over Torque” lights
3
Detect overtorque at any time. Continue operation after detection.
(Miner fault)
“Over Torque” blinks
4
Detect overtorque at any time. Stop output after detection (Fault)
“Over Torque” lights
(13) Output Voltage Limitation Selection (Sn-13)
•
In low speed region, if the output voltage from V/f pattern is too high, the inverter
will be driven into fault status. As a result, the user can use this option to set the
upper bound limit of output voltage.
Output
Voltage
Output Frequency
Cn-04
Cn-04
40
(Output frequency at Max. output voltage)
Output Voltage Bound
(double the value for 440V class)
0
5V
40V
250V
Fig. 34 Output voltage limit