103
(13)PID Control Input
(Un-15)
(14)PID Control Output1 (Un-16)
(15)PID Control Output2 (Un-17)
•
The values in Fig. 14 (on page 42) can be monitored through the parameters of
Un-15, Un-16 and Un-17. Moreover, the multi-function analog output terminal
AO1, AO2 can be used to monitor the output value through the proper setting of
Sn-33 and Sn-34.
(16)Message 1
(Un-18)
(17)Message 2
(Un-19)
(18)Message 3
(Un-20)
(19)Message 4
(Un-21)
•
These parameters are used to display the fault messages whenever the fault
occurred. The user can take proper action for trouble-shooting based upon the
displayed message.
(20)The Cumulative Operation Time Setting
(Un-22)
•
The parameter is used to count the elapsed time from the previous fault to the
latest fault occurred recently. Its setting range is 0~65536 Hr. After the fault have
been cleared and system reset again, the Un-22 will be cleared to zero and counted
again.
(21)The Frequency Command While Last Fault Occurred
(Un-23)
(22)The Output Frequency While Last Fault Occurred
(Un-24)
(23)The Output Current While Last Fault Occurred
(Un-25)
(24)The Output Voltage While Last Fault Occurred
(Un-26)
(25)The DC Voltage While Last Fault Occurred
(Un-27)
(26)The Input Terminal Status While Last Fault Occurred
(Un-28)
(27)The Output Terminal Status While Last Fault Occurred (Un-29)
•
The above parameters will display the inverter status when the fault occurred
lately. The contents of parameters Un-15~21 will be cleared after the faults have
been cleared and the system reset again.
(28)The Cumulative Time Whenever The Input Power Is On
(Un-30)
•
The parameter will record the cumulative operation time from power-on to power-
off. Its value is 0~65536 Hr. If the value exceed 65536, it will restart from 0 again.
(29)The Cumulative Run Time Whenever The Output Power Is On (Un-31)
•
The parameter will record the cumulative operation time from power-on to power-
off. Its value is 0~65536 Hr. If the value exceeds 65536, it will restart from 0
again.
(30)The EPROM Software Version
(Un-32)
•
The parameter will specify the updated software version in this 7200 MA inverter.
(31)Motor Speed While PG Feedback Is Set.
(Un-33)
•
While PG feedback control is set, The motor speed can be monitored through Un-33.