Table 13 V/F curve of 3~20 HP, 220V Class MA inverter *
Specifications
Sn-02
V/F Pattern
†
Specifications
Sn-02
V/F Pattern
†
Low
Starting
Torque
08
50Hz
00
(00)
50
1.3 2.5
220
7.5
14
0
(Hz)
(V)
50Hz
High
Starting
Torque
09
(08)
50
1.3 2.5
220
7.6
15.2
0
(Hz)
(V)
(09)
14.6
7.7
60Hz
Satu-
ration
01
15
Low
Starting
Torque
10
60Hz
50Hz
Satu-
ration
02
(02)
60
1.5 3
220
7.5
14
0
(Hz)
(V)
(01),(15)
50
High Staring T
o
rque
‡
60Hz
High
Starting
Torque
11
(10)
60
1.5 3
220
7.6
15.2
0
(Hz)
(V)
(11)
14.6
7.7
General Purpose
72Hz
03
(03)
72
1.5 3
220
7.5
14
0
(Hz)
(V)
60
90Hz
12
(12)
90
1.5 3
220
7.5
14
0
(Hz)
(V)
60
Variable
Torque 1
04
50Hz
Variable
Torque 2
05
(05)
50
1.3
25
220
6.8
7.5
0
(Hz)
(V)
38.5
55
(04)
120Hz
13
(13)
120
1.5 3
220
7.5
14
0
(Hz)
(V)
60
Variable
Torque 3
06
V
ariable T
o
rque Characteris
tic
60Hz
Variable
Torque 4
07
(07)
60
1.5
30
220
6.8
7.5
0
(Hz)
(V)
38.5
55
(06)
Rated Output Operation (Machine T
ool)
180Hz
14
(14)
180
1.5 3
220
7.5
14
0
(Hz)
(V)
60
* These values are for the 220V class; double the values for 440V class inverters.
† Consider the following items as the conditions for selecting a V/f pattern.
They must be suitable for
(1) The voltage and frequency characteristic of motor.
(2) The maximum speed of motor.
‡ Select high starting torque only in the following conditions. Normally, the
selection if not required.
(1) The power cable length is long [492ft (150m) and above].
(2) Voltage drop at startup is large.
(3) AC reactor is inserted at the input side or output side of the inverter.
(4) A motor with capacity smaller than the maximum applicable inverter capacity
is used.