98
(47) LCD Language Displayed Selection (Sn-62)
•
Sn-62 = 0 : English
= 1 : Chinese
(48) Parameter Copy (Sn-63)
•
JNEP-31 LCD digital operator can upload the parameter settings from the LCD
digital operator to inverter and download parameter settings from the inverter to
the LCD digital operator.
•
LCD digital operator will check its EEPROM or the inverter’s EEPROM under the
following settings.
•
Sn-63 = 0 : NO action
= 1 : Upload data (LCD digital operator
→
inverter). During this period, the
LED on the LCD digital operator will light sequentially in the CW
sense.
= 2 : Download data (inverter
→
LCD digital operator). During this period,
the LED on the LCD digital operator will light sequentially in the
CCW sense.
= 3 : Verification check on LCD’s EEPROM; during this period the LED
will be switch-on between 2 groups.
= 4 : Verification check on inverter’s EEPROM; during this period the LED
will not light.
•
Please follow the below steps to implement the action of parameter copy between
different inverters (either upload or download).
Step 1 : Check the contents of (LCD) digital operator EEPROM (Sn-63=’03’),
then check the contents of inverter’s EEPROM (Sn-63=’04’). Make sure
that both EEPROM function properly.
Step 2 : Download and copy the inverter’s parameter settings to LCD digital
operator EEPROM (Sn-63=2).
Step 3 : Upload and copy the parameter settings of LCD digital operator to other
inverter’s EEPROM (Sn-63=1).
(49) PID Function Selection (Sn-64)
•
To enable PID control, set Sn-64=1. Otherwise, set Sn-64=0 to disable PID control
function. Moreover, it is possible to use the multi-function terminals
○
5 ~
○
8 to
enable/disable PID control.