4
1.2 Installation
When installing the inverter, always provide the following space to allow normal
heat dissipation.
50 mm min.
30 mm
min.
30 mm
min.
50 mm
min.
ambient
temperature
-10 ~ + 40
℃
AIR
AIR
120 mm
min.
120 mm
min.
(a) Space in Side (b) Space in Top/bottom
Fig. 1
Air clearance for 7200MA wall mounting
CAUTION
Location of equipment is important to achieve proper performance and normal
operating life. The 7200MA-model unit should be installed in area where the
following conditions exist.
•
Ambient temperature : -10
o
C
∼
+40
o
C
•
Install 7200MA in a location free from rain, moisture and not in direct sunlight.
•
Install 7200MA in a location free from harmful mist, gases, liquids, dusts and
metallic powder.
•
Install 7200MA in a location without excessive oscillation and electromagnetic
noise.
•
If more than 1 inverter are installed in a box, be sure to add a cooling fan or air
conditioner to maintain the air temperature below +45
o
C.