![TECO speecon 7200ma Instruction Manual Download Page 104](http://html1.mh-extra.com/html/teco/speecon-7200ma/speecon-7200ma_instruction-manual_1072473104.webp)
102
(1) Frequency Command
(Un-01)
(2) Output Frequency
(Un-02)
(3) Output Current
(Un-03)
(4) Output Voltage
(Un-04)
(5) Main Circuit DC Voltage (Un-05)
•
Through the settings of Sn-33, Sn-34, the above contents can be displayed at the
multi-function analog output terminals (AO1, AO2) in different voltage level of
(0~10V)
(6) External Analog Command VIN (Un-06)
•
The parameter can monitor the external analog terminal voltage VIN
(0~100%/0~10V). The voltage can be output through the multi-function analog
output terminal AO1, AO2 (Sn-33=05 or Sn-34=05). The output voltage is the PID
feedback voltage when the PID function is used. Please refer to page 42, “PID
controller block diagram”.
(7) External Analog Command AIN (Un-07)
•
The parameter can monitor the external analog terminal current AIN
(0~100%/0~20mA). The current can be output through the multi-function analog
output terminal AO1, AO2 (Sn-33=06 or Sn-34=06). The output current is the PID
feedback voltage when the PID function is used. Please refer to page 42, “PID
controller block diagram”.
(8) Multi-Function Analog Input Command AUX (Un-08)
•
The parameter can monitor the multi-function analog input terminal AUX voltage
(0~100%/0~20mA). The voltage can be output through the multi-function analog
output terminal AO1, AO2 (Sn-33=07 or Sn-34=07). The output voltage is the PID
target voltage (reference) when the PID function is used. Please refer to page 42,
“PID controller block diagram”.
(9) External Analog Output AO1, AO2
(Un-09, Un-10)
•
The parameter can monitor analog output terminal AO1, AO2 voltage (0~10V).
Their output gain can be adjusted through the setting of parameters Bn-14 or Bn-
15. Their outputs are determined and varied proportionally according to the setting
of (Sn-33 or Sn-34).
(10)Input Terminal Status
(Un-11)
•
The parameter will monitor the status of input terminal
○
1 ~
○
8 : ‘ON’ or ‘OFF’.
(11) Output Terminal Status (Un-12)
•
The parameter will monitor the status of input terminal RA-RC or R1A-R1C,
DO1-DOG, DO2-DOG or R2A-R2C : ‘ON’ or ‘OFF’.
(12)PG Speed Feedback and PG Speed Compensation (Un-13, Un-14)
•
These parameters will monitor the PG speed feedback and PG speed compensation
signal if PG feedback function is used.