CHAPTER 10 – OPTIONS
10.1 - RS-485 SERIAL INTERFACE
Should you will need a network connection, please contact
for technical support.
The RS-485 serial expansion card allows the control unit to be networked to other weld control units and to a
central personal computer to program the control unit or to document production data. The card interfaces with
the control unit through a 6-pin connector and with the external network through a standard male 9-pin
connector with the following signals:
PIN 1
Ground
PIN 2
Y (TX+)
PIN 3
A (RX+)
PIN 4
R1A
PIN 5
R2A
PIN 6
Z (TX-)
PIN 7
B (RX-)
PIN 8
R1B
PIN 9
R2B
The card can be connected only when the control unit is not powered-on. It is also advisable to first connect the
6-pin twin wire, which connects the weld control unit, and then the RS485 connection. Then power on the control
unit and activate the
NET/485
function in the SETUP MENU.
During the network communication, the weld control unit (slave) requires the assignment of an identification
address in order to be recognized by a Master, a Personal Computer for example. Even this parameter, called
ADDRESS, is set in the SETUP MENU.
In order to manage data and communication between the networked control units, there is a PC software called
"
Net"
designed to check the network structure, i.e. how many and which control units are connected,
remotely performing the programming in each control unit and acquiring and saving production data.
The interface is isolated up to 1500V, without the need for any external power supply and works as a connection
with standard RS485 signals in half duplex or full duplex mode. The male D-sub nine-pin connector has two
screws with 4-40 UNC threading that also have a threaded head. These screws will be used for wall-mounting
purposes (max 3mm) and for locking the mobile connector. The card is fitted with a protective black cap that
protects it from dust and electrostatic charges. It is advisable to always leave this cap on the card's connector
when the interface is not used.
The cards are fitted with termination resistances to be connected only to the first and last network connector. Do
not forget to connect the ground wire among the various devices connected to the network.
The cable that connects the devices must not be longer than 1200 m, it must be shielded and have metallic or
metallized connecting connectors. We recommend using Belden 8777 cable at 24 AWG with "Phoenix"
"SUBCON 9/F – SH" type connectors.