5.1.4 SYMPTOMS & PARTS TO INSPECT
Serial communication errors & mis-setting
Maintenance
remocon
alarm
display
Alarm
contents
Judgement conditions
clearing
condition
Judgement and correction
E01
Maintenance
Remocon detected
error signal from
A2 board
Serial signal receiving failure
Automatic
recovery
1. Check remocon connection
2. Check address on A2 board
3. Check A2 board
E02
Serial signal sending failure
E03
A2 board detected
error signal from
remocon
Serial signal failure
Automatic
recovery
1. Check remocon connection
2. Check remocon configuration (see part 6)
3. Check address on A2 board
4. Check A2 board
E04
A2 board detected
error signal from
A3 board
Serial signal receiving failure
Automatic
recovery
1.Check connection between boards
(OC connector)
2. Check addresses – if necessary, launch
auto address sequence
3. Check boards
E05
Serial signal sending failure
E06
A3 board detected
error signal from
A2 board
Serial signal receiving failure
Automatic
recovery
Automatic
recovery
1. Check connection between boards
(OC connector)
2. Check A2 and A3 boards.
E07
Serial signal sending failure
E15
Automatic address
setting failure.
A2 capacity/number
parameters (too low)
Power supply
reset
recovery
1. Check A2 parameters (see Part 6) - if
necessary, launch auto address sequence
2. Check connection between boards (OC
connector)
3. Check A2 board
4. Check A3 board
E16
A2 capacity/number
parameters (too low)
E20
A3 board cannot receive any
serial signals from A2 board.
E22
Mis-wiring error
Mis-wiring between boards
or
Missing phase on power
supply
Power supply
reset
recovery
1. Check wiring.
2. Check power supply connections
E31
(*)
Communications
trouble within
boards
No communication possible
with MDC for 3 minutes or
longer
Automatic
recovery
Check A3 board
Refer to diagnosis method (section 5.1.5)
(*) see detail § 5.1.5
Summary of Contents for PHIE 095
Page 2: ...2...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12 1 3 2 THREE PHASES MODELS...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Page 18: ...18...
Page 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Page 20: ...20 1 5 2 THREE PHASES MODELS...
Page 22: ...22...
Page 23: ...23...
Page 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Page 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Page 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Page 43: ...43 Failure matrix...
Page 44: ...44 Failure handling...
Page 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Page 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Page 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Page 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Page 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Page 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Page 55: ...55 3 1 4 SYMBOLS...
Page 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Page 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Page 77: ...77 A4 Supply and filter board for units 257 307...
Page 101: ...101 For models 257 307...
Page 104: ...104 For models 095 125 Replace A3 PCB...
Page 105: ...105 For models 155 157 175 177 195 197...
Page 106: ...106 For models 257 307...
Page 107: ...107 For models 095 125...
Page 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...