Here below the system control alarms list concerning the heat pump itself
Sensors failure
System ctrl
box
alarm
display
Alarm
contents
Judgement conditions
clearing
condition
Judgement and correction
SEin
Disconnection, open
circuit or short
circuit
in system water inlet
temperature
S11
Open circuit or short circuit
Automatic
recovery
1. Check water inlet temperature sensor S11
2. Check connection
3. Check A1 board
SEOu
Disconnection, open
circuit or short
circuit
in system water
outlet temperature
S12
Open circuit or short circuit
Automatic
recovery
1. Check water outlet temperature sensor S12
2. Check connection
3. Check A1 board
SAE
Disconnection, open
circuit or short
circuit
in system outdoor
temperature
S13
Open circuit or short circuit
Automatic
recovery
1. Check outdoor temperature sensor S13
2. Check connection
3. Check A1 board
Heat pump defaults
System ctrl
box
alarm
display
Alarm
contents
Judgement conditions
clearing
condition
on system
Judgement and correction
Gr
Synthetic heat pump
alarm
transmitted to
system control
See § 5.1 & 5.2
Manual reset
See § 5.1 & 5.2
HE
Electric support
heater default
• Water pressure in heat
pump circuit too low
• Safety thermostats on
heater activated
(80°C for auto reset
115°C for manual reset)
Automatic
recovery
1. Check water pressure in heat pump circuit
2. Check water flow in heat pump circuit
3. Check thermostats and their connection
! Important !: in case of manual reset
thermostat action, check carefully if any
components (insulation, heater,...) have
been damaged.
Replace parts if necessary.
Check also the operation of the automatic
reset thermostat.
FL
Water flow default in
heat pump
See § 5.2
Manual reset
See § 5.2
Cn
System
communication
failure
Communication line
between A1 & A2 board
defective
Automatic
recovery
1. Check wiring and connections”
2. Check line supply (LED “SC” on A2 /LED” C”
on A1lighted glittering)
3. Check system configuration (parameters)
4. Check board A2
5. Check board A1
Summary of Contents for PHIE 095
Page 2: ...2...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12 1 3 2 THREE PHASES MODELS...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Page 18: ...18...
Page 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Page 20: ...20 1 5 2 THREE PHASES MODELS...
Page 22: ...22...
Page 23: ...23...
Page 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Page 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Page 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Page 43: ...43 Failure matrix...
Page 44: ...44 Failure handling...
Page 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Page 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Page 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Page 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Page 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Page 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Page 55: ...55 3 1 4 SYMBOLS...
Page 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Page 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Page 77: ...77 A4 Supply and filter board for units 257 307...
Page 101: ...101 For models 257 307...
Page 104: ...104 For models 095 125 Replace A3 PCB...
Page 105: ...105 For models 155 157 175 177 195 197...
Page 106: ...106 For models 257 307...
Page 107: ...107 For models 095 125...
Page 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...