89
4.16 HEAT PUMP STAND ALONE OPERATION
Performed by A2 board -
see presentation § 3.2.4
For the maintenance and commissioning operations, the heat pump can be operated in a “stand-alone”
configuration, without system control, using the specific maintenance remocon (see PART 6) and/or external
voltage free contacts.
The system can be disconnected in two ways:
- Either, with power off, disconnect the system communication line "BUS" from A
2
board (connector “
SC
”).
- Or, by the system control unit, deactivate heat pump control by setting parameter 76 to "
0
" – see System
control
manual.
To operate the heat pump, force the circulating pump (see § 4.12) before initiate an order via the specific
maintenance remote control or the external contacts.
Heat pump control with voltage free external contacts:
Inputs for external contacts are available on
A2
(CWC2) board in order to force heat pump operation
(
ON / OFF - Heat / cool
). These inputs have priority to the control signals initiated by means of the possible
maintenance remote control.
The state of these inputs is indicated by the lights placed on the board. Set points (heat and cool) must be adjusted by
the maintenance remote control but for operation and control by contacts, maintenance remote control is not
mandatory.
ON/OFF:
-Closing a contact between “
C
” and “
1
” on the terminals block “
ON/OFF
” makes the unit starts.
Corresponding LED is lighted in green.
-Closing a contact between “
C
” and “
0
” on the terminals block “
ON/OFF
” makes the unit stops.
Corresponding LED is lighted in red.
In case of closing both contacts at the same time, priority is given to “
OFF
”.
Note:
on A2 board in versions 01 & 02, “
OFF”
input is also active with system control connected.
HEAT / COOL:
-Closing a contact between “
C
” and “
1
” on the terminals block “
HEAT/COOL
” selects “
HEAT
” mode.
Corresponding LED is lighted in red.
-Closing a contact between “
C
” and “
0
” on the terminals block “
HEAT/COOL
” selects “
COOL
” mode. Corresponding
LED is lighted in green.
In case of closing both contacts at the same time, priority is given to “
HEAT
”.
Note:
on A2 board in versions 01 & 02, “
HEAT
” input is also active with system control connected.
A voltage free change-over contact (use in 24 V max.) is available on
A2
(CWC2) board for remote heat pump alarm
signaling.
4.17 HEAT PUMP ALARM SIGNAL FOR SYSTEM CONTROL
Performed by A2 board -
see presentation § 3.2.4
Heat pump faults coming from the frigorific circuit are classified in 2 categories:
-
Manual reset faults
:
Memorized by board A2 as soon as they appear and transmitted to the system control. The A2 board alarm light
“AL” comes on steady.
-
automatic reset faults
:
The A2 board alarm light “AL” flashes as soon as a fault appear. If it lasts longer than 30 minutes, fault is memorized in
board A2 and transmitted to the system control. The alarm light “AL” then remains steady.
The detailed list of faults is indicated in part 5.
To determine the exact nature of the fault, refer to
LED1 & LED2
on the power board A3
or connect the specific
maintenance remocon to the heat pump (see Part 6).
Summary of Contents for PHIE 095
Page 2: ...2...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12 1 3 2 THREE PHASES MODELS...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Page 18: ...18...
Page 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Page 20: ...20 1 5 2 THREE PHASES MODELS...
Page 22: ...22...
Page 23: ...23...
Page 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Page 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Page 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Page 43: ...43 Failure matrix...
Page 44: ...44 Failure handling...
Page 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Page 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Page 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Page 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Page 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Page 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Page 55: ...55 3 1 4 SYMBOLS...
Page 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Page 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Page 77: ...77 A4 Supply and filter board for units 257 307...
Page 101: ...101 For models 257 307...
Page 104: ...104 For models 095 125 Replace A3 PCB...
Page 105: ...105 For models 155 157 175 177 195 197...
Page 106: ...106 For models 257 307...
Page 107: ...107 For models 095 125...
Page 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...