5-4 BOARDS REPLACEMENT
WARNING:
Before carrying out any work on the machine, make sure that its power supply is switched off and the access to it is
prevented.
Any work must be carried out by personnel qualified and authorized to work on this type of machine.
5.4.1 A2 BOARD REPLACEMENT
IMPORTANT: Some setting data (parameters) specific to each type of heat pump are stored in the EEPROM on
the (A2/CWC2) control board.
When replacing a PCB, it is necessary to remove the EEPROM from the malfunctioning
board and re-install it on the
new board.
Procedure:
1) B
efore replacing the board (A2), make sure that the unit is switched off (“Power” LED - red - is Off).
2) Disconnect completely all wires and connectors from the board.
3) Remove the board by pulling it off from the spacers (4).
4) Take out from the old board the EEPROM and possible wire jumper.
5) Plug the EEPROM (and possible jumper) on the specific socket of the new board. Respect position of the
EEPROM on its socket (see picture above). Be
careful when handling the EEPROM, as its pins can be easily bent.
6) Make sure that micro switches SW1 / SW2 and jumpers JTP / JPC are in the right selection – refer to § 3.2.4 and
picture above.
7) Install the new board on the spacers and connect it while respecting wiring diagram.
8) Switch on again the unit. LED “Power” must be lighted on (If this LED is blinking or is off, check that EEPROM is
installed correctly).
9) Start the unit and check its correct operation.
Caution:
If the EEPROM is not functioning correctly, a
larm F29 appears. In that case, EEPROM must be changed also
(use the one delivered with the new board). Then, parameters specific to the unit must set in the EEPROM, by means
of service remote control, before starting again the unit. For that refer to part 6.
Summary of Contents for PHIE 095
Page 2: ...2...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12 1 3 2 THREE PHASES MODELS...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Page 18: ...18...
Page 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Page 20: ...20 1 5 2 THREE PHASES MODELS...
Page 22: ...22...
Page 23: ...23...
Page 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Page 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Page 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Page 43: ...43 Failure matrix...
Page 44: ...44 Failure handling...
Page 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Page 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Page 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Page 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Page 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Page 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Page 55: ...55 3 1 4 SYMBOLS...
Page 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Page 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Page 77: ...77 A4 Supply and filter board for units 257 307...
Page 101: ...101 For models 257 307...
Page 104: ...104 For models 095 125 Replace A3 PCB...
Page 105: ...105 For models 155 157 175 177 195 197...
Page 106: ...106 For models 257 307...
Page 107: ...107 For models 095 125...
Page 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...