97
Mis-setting
Maintenance
remocon
alarm
display
Alarm
contents
Judgement conditions
clearing
condition
Judgement and correction
L02
A2 and A3 boards
settings are
incompatible
A2 board judged
incompatible
with A3 board
(wrong spare part or
wrong parameters setting)
Power reset
recovery
1. Check setting parameters in the EEPROM of A2
2. Check A2 board
3. Check setting parameters in the EEPROM of A3
L08
Settings failure
Incorrect address in
EEPROM of A2 board.
Power reset
recovery
Check address setting in the EEPROM of A2
board
L09
Settings failure
Incorrect capacity in
EEPROM of A2 board.
Power reset
recovery
Check capacity setting in the EEPROM of A2
board
L10
Settings failure
Capacity not set in
EEPROM of A3 board
Power reset
recovery
Check capacity setting in the EEPROM of A3
board
L13
Settings failure
A3 and A2 board types of
unit judged incompatible
(wrong spare part or
wrong parameters setting)
Automatic
recovery
1. Check setting parameters in the EEPROM of A2
2. Check A2 board
3. Check setting parameters in the EEPROM of A3
4. Check A3 board
Summary of Contents for PHIE 095
Page 2: ...2...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12 1 3 2 THREE PHASES MODELS...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Page 18: ...18...
Page 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Page 20: ...20 1 5 2 THREE PHASES MODELS...
Page 22: ...22...
Page 23: ...23...
Page 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Page 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Page 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Page 43: ...43 Failure matrix...
Page 44: ...44 Failure handling...
Page 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Page 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Page 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Page 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Page 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Page 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Page 55: ...55 3 1 4 SYMBOLS...
Page 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Page 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Page 77: ...77 A4 Supply and filter board for units 257 307...
Page 101: ...101 For models 257 307...
Page 104: ...104 For models 095 125 Replace A3 PCB...
Page 105: ...105 For models 155 157 175 177 195 197...
Page 106: ...106 For models 257 307...
Page 107: ...107 For models 095 125...
Page 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...