75
UNITS 257 / 307 – COMMENTS
•
S002 rotary switch
(10 positions, black)
/ S003 DIP switches
(2P, blue)
:
Address for split air to air units – not used for the application.
The factory setting below must not be changed :
•
CN047 Auto address plug
(2P, white)
:
Normally, the addressing sequence between refrigerant circuit power board A3 and control board A2 takes place when power is
initially turned on at the factory.
In case of board replacement or problem of communication on the field, it can be necessary to launch again an addressing
sequence. For that, short circuit the pins of the plug.
During automatic address setting, LEDs 1 & 2 are blinking alternatively (open circuit these pins stops automatic address
setting).
After the power is turned ON, automatic address setting will not be functioned for over 1 minute and 30 seconds.
•
CN048 Pump down plug
(2P, white)
:
Used for split air to air units for refrigerant recovery sequence – not used for the application.
•
CN039 RC-P Service remocon connection plug
(5P, red)
:
See PART 6
•
CN033 Test plug
(2P, red)
:
Used for PCB inspection in factory.
•
CN038 MODE plug
(2P, white)
:
Not used.
•
CN501 ROM plug
(4P, white)
:
Used for PCB software loading in factory with “PAC checker” interface.
•
CN030 EXCT plug
(3P, red)
:
Designed for capacity control – not used.
•
CN037 SILENT (or QUIET) MODE plug:
Software version:
Unit Version
Date
257 (8HP)
V110
Jan. 2012
307 (10HP)
Summary of Contents for PHIE 095
Page 2: ...2...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12 1 3 2 THREE PHASES MODELS...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Page 18: ...18...
Page 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Page 20: ...20 1 5 2 THREE PHASES MODELS...
Page 22: ...22...
Page 23: ...23...
Page 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Page 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Page 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Page 43: ...43 Failure matrix...
Page 44: ...44 Failure handling...
Page 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Page 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Page 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Page 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Page 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Page 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Page 55: ...55 3 1 4 SYMBOLS...
Page 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Page 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Page 77: ...77 A4 Supply and filter board for units 257 307...
Page 101: ...101 For models 257 307...
Page 104: ...104 For models 095 125 Replace A3 PCB...
Page 105: ...105 For models 155 157 175 177 195 197...
Page 106: ...106 For models 257 307...
Page 107: ...107 For models 095 125...
Page 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...