Error Message
Reason
Remedial Measure and
Explanation
Red LED is permanently lit
The different positions
in the
“Program
Mode
”
have not been
programmed in the
right order, e.g. Value
1 „upper reduced start
point
“ is larger than
value 2 „pre-crimp
holding point“ of the
contact.
Pay attention to the right
positioning of the heights.
The order has to be as follows:
Value 1 < Value 2 < Value 3
Red LED is permanently lit
+ Display Message
Oil temperature is too
high or oil level is
below the minimum.
Cool down hydraulic unit and
search for the reason of the
temperature rise!
Refill hydraulic oil.
Red LED is permanently lit
+ Display Message
Pressure sensor
provides incorrect
values or a cable
broke.
Check pressure sensor and
cables.
Restart the control system.
Red LED blinks cyclically
Stroke measuring
system is faulty. No
signal can be received.
The cylinder cannot be
moved.
Check the magnetic slider.
Check whether the sensor is
connected to CAN and to power
supply.
Check the position magnet.
Display Message
CAN communication
for control or CAN IO
control failed.
System has to be restarted.
Check possible sources of
interference for CAN Bus.
Restart the control system.
OIL-NIV
OIL-TEMP
P-SENSOR
FAILURE
PLC / CAN
ERROR!