7) Reference material: Parameter setting values at the factory shipment and upper
and lower limit values
Parameter
Unit
Initial
Value
Lower
Limit
Upper
Limit
Note
Symbol
Name
CVB
Target Battery
Volts
V
48
32
62
If the Battery Over Charging
Protection is enable, the
parameter is used for limit of
battery voltage of charging.
DRB
Droop Ratio of
Battery
rate 0
0
3.999
When set to 0.01 (1%), the
battery target voltage drops by
0.48 V at 52A output.
I
t should be noted that the
input unit in CNVCommCC is
"%".
DVG
Target Grid Volts
V
320
260
390
Upper limit voltage is 380V
in the specification.
DRG
Droop Ratio of
Grid
rate 0
0
3.999
When set to 0.01 (1%), the
grid target voltage drops by
3.8 V at 7.8A output.
It should be noted that the
input unit in CNVCommCC
is "%".
CIB
Current Limit of
Battery
A
52.006 0
56.77
Nominal value is 52A.
DIG
Current Limit of
Grid
A
7.8001 0
8.5162 Nominal value is 7.8A.
OBV
Over Battery Volts V
64
32
68
Heavy alarm while the
control target is operating
on the battery side, light
alarms in others.
UBV
Under Battery
Volts
V
32
32
68
Light alarm at standby,
heavy alarm at running.
OGV
Over Grid Volts
V
400
260
410
Standby and the charging in
Manual CV mode, is a light
alarm, others are heavy
alarm.
UGV
Under Grid Volts
V
290
260
410
Standby and the charging in
Manual CV mode, is a light
alarm, others are heavy
alarm.
CDB
Deviation of Volts
for Warning of
Charging Upper
Limit
V
1.002
0
12
Set deviation of volts for
warning of charging upper
limit, When Battery
Volt>CVB-CDB, Warning
signal is outputted.