- 23 -
TDK-Lambda
EZA2500 series
Quick Manual / Basic
Parameter
Unit
Initial
Value
Lower
Limit
Upper
Limit
Note
Symbol
Name
CCR
Deviation of Volts
for Cancel
Warning of
Charging Upper
Limit
V
0
0
12
When Battery Volt<CVB-
CDB-CCR, Warning signal is
canceled.
DLB
Limit of Battery
Volts for
Discharging
V
33
32
64
Set the limit of battery
voltage for discharging.
This parameter is used for
Battery over discharge
protection. Set a value
larger than UBV.
DDB
Deviation of Volts
for Warning of
Discharging
Lower Limit
V
1.002
0
12
Set deviation of volts for
warning of discharging lower
limit
、
When Battery
Volt<DLB+DDB, Warning
signal is outputted.
DDR
Deviation of Volts
for Cancel
Warning of
Discharging
Lower Limit
V
0
0
12
When Battery Volt
>DLB+DDB+DDR, Warning
signal is canceled.
PDZ
Plus side volts for
Dead Zone in
Automatic Grid
CV mode
V
0
0
57
Set plus side volts for dead
zone. When Grid voltage is
between DVG and
DVG+PDZ, EZA do not
charge or discharge in Grid
Automatic CV mode.
BCF
Battery Configure
Function (Flag
bit allocation)
―
0
0
7*
bit0:Overcharge protection
(1:Enable 0:Disable)
bit1:Over discharge
protection (1:Enable
0:Disable)
bit2:Battery Rump up
(1:Enable 0:Disable)
* If you enter more than 8,
EZA will be recognized as 7.