23 

Weights & Measures

 

REGISTER #   

Highlight Register # and input the TCS 3000 serial number located on the unit.  Press  

 

 

 

ENTER when complete. 

 
TRUCK ID 

 

Highlight Truck ID to input the truck or tank number.  Press ENTER when complete. 

 

 

 

NOTE: if there are multiple meters daisy chained together, the Truck ID and Meter 

 

 

 

sequence number should be input here. 

 
METER VERSION 

Highlight Meter Version and enter the manufacture.  Press ENTER when complete. 

 
METER MAKE   

Highlight Meter Make and enter the meter manufacturer’s name and Press ENTER 

 

 

 

when complete. 

 
METER MODEL 

Highlight Meter Model and enter the assembly model number.  Press ENTER when  

 

 

 

complete. 

 
METER SERIAL # 

Highlight Meter Serial # and input the meter serial number of the unit.  Press ENTER when 

 

 

 

complete. 

 
SYSTEM ID 

 

Highlight System ID and input the system identification.  Press ENTER when complete. 

 

6) PROVER TICKET

 

 

 

 

 

Selecting Prover Ticket allows you to Print the existing Prover Data from the TCS 3000.   

 

 

 

Select PRINT to print the Prover Ticket. 

 

7) TICKETS CLEANUP  

 

 

 

 

Enabling Tickets Cleanup will allow the system to delete the oldest 500 non-printed tickets  

 

 

 

when there are more than 5000 non-printed tickets stored.   

 
 

 

 

 

*This Might Not Be Legal in Some Countries or States 

 

8) RESET TOTALISERS  

 

 

 

 

System and Product Totalizers record the amount of all liquid that has passed  

 

 

 

through the meter by product.   

 

* Please Note *

 

Resetting the Totalizers will reset the TCS 3000 Totalizers to zero.  There is no way to recover totalizers once 

deleted.

 

 
 

SYSTEM TOTALIZER   
 

 

 

System Totalizers record the amount of all liquid that has been measured. 

 

 

 

End Shift before resetting the System Totalizer.  Highlight the System Totalizer and press 

 

 

 

ENTER.  A “WARNING” will appear on the screen that you are about to reset the 

 

 

 

Totalizers.  Press MODE to  confirm the Totalizer reset. 

 
PRODUCT TOTALIZER

  

 

 

 

Product Totalizers record the amount of liquid for a specific product that has been measured. 

 

 

 

You must End Shift and Deactivate Product in Product Settings (page 22) before resetting 

 

 

 

the Product Totalizer.  Without doing so, the error “No Active Products” will be displayed.  

 

 

 

Highlight Product Totalizer and press ENTER.   

 

9) ENABLE REMOTE CONFIG 

 

 

 

 

Allows you to connect the TCS 3000 to a F-RAMS handheld device to remotely  

 

 

 

control the Calibration of the register. 

 
 

 

 

- To Enable Remote Config make sure your F-Rams handheld is connected to the TCS  

 

 

 

  3000 register with the TCS 300859 quick disconnect cable kit). 

 

 

 

- Highlight Remote Config and select ENTER.  This will enable the Remote Config setting 

 

 

 

  and you will be able to calibrate your system. 

 

 

 

-

 When finished calibrating, press any key to exit.

 

Summary of Contents for TCS 3000

Page 1: ...Catalog Title Catalog Subtitle Setup Operation Manual TCS 3000 REGISTER...

Page 2: ...Calibration 32 Trouble Shooting 33 Trouble Shooting Continued 34 Trouble Shooting Continued 35 Trouble Shooting Continued 36 Notes 37 Notes 37 Warranty 39 Table of Contents 2 Receipt Inspection 3 Not...

Page 3: ...egister unless stated Removing register assembly from packaging without adhering these warn ings may cause serious injury to you and or the register Appropriate precautions should be taken regarding a...

Page 4: ...the TCS 3000 to improve your product security and ease access to your delivery data to reduce your operation costs Many additional features are available multiple product delivery additive injection...

Page 5: ...unexpected operation inaccurate measure ments and damage to equipment or property Navigation Keyboard Functions Start Enter Key Stop Cancel Key Arrow Keys Power Light Power Light Allows you to see tha...

Page 6: ...rint Key Allows you to print You can print the delivery with or without selecting the STOP key Shift Key Allows you to select the Alpha Keys on the Alpha Numeric Keys Selecting Shift allows you to use...

Page 7: ...ices W M Settings Product Setup and Calibration Product Settings Product Activation Price Settings and Device Time Settings Advanced Functions System Software Update SELECT FUNCTION Start Delivery 1 S...

Page 8: ...nly accurate as the driver operators that utilize this feature 1 BEGIN SHIFT Press and hold the SHIFT key then press the MODE key 2 END SHIFT Press and hold the SHIFT key then press the MODE key 3 Aft...

Page 9: ...ngs Configuration of system functions Display Settings Configure display screens and fields Printer Settings Select printer host remote or none Regional Settings Date and Time settings Delivery Settin...

Page 10: ...ing delivery and start up Configure Type 1 Using the arrow keys to move around the screen highlight the field you would like to change and select ENTER The field options are in Table 1 below Configure...

Page 11: ...sible Auto Net Totalizer is visible only when a product has Automatic Temperature Correction ATC enabled on a Product Never net Totalizer is never visible GROSS TOTALIZER Gross Totalizer allows you to...

Page 12: ...r a single printer Host is the primary meter and the Clients are all registers following the Host Enable Disable Host To Enable or Disable the Printer Host highlight Enable or Disable and select ENTER...

Page 13: ...mmable Field Customer ID 2 Programmable Field Customer ID 3 Programmable Field Customer ID 4 Programmable Field Line Delivery Gross Begin Delivery Gross End Delivery Net Begin Delivery Net End TempCom...

Page 14: ...Preset Enable or disable preset for repeat BATCH presets MULTIPLE DELIVERIES Allows for the user to fill multiple tanks on one 1 single ticket transaction Simply press and hold the SHIFT key down whi...

Page 15: ...r serial communication to an ancillary display that will read the same data that is displayed on the TCS 3000 register Enable Disable Enable or disable and press ENTER Configure Select Type Red Lion L...

Page 16: ...s Network Settings Interface Interface is for handheld communication An interface is required for this setting Address Device Address will assign the TCS 3000 the unique address within the Daisy Chain...

Page 17: ...c password and press ENTER 4 Confirm password entry by resubmitting password and press ENTER NOTE Alphanumeric password must be at least three 3 characters long Access Key Access Key is used to lock o...

Page 18: ...nd select ENTER If you need to modify the settings you originally selected for the calibration of a product select MODIFY PA RAMETERS if the settings were correct and you do not need to change them se...

Page 19: ...er how long you wish the Pump Starter stays powered Enter value in Seconds and press ENTER Valve Type Select whether you are using a Single or Dual Stage Valve and press ENTER A Single Stage valve wil...

Page 20: ...change the Totalizer unit of measure See Page 21 for changing Totalizer unit of measure Temperature Highlight Temperature Unit and press ENTER Currency Select the Currency Symbol or Abbreviation and p...

Page 21: ...alibration Value Press STOP to finish C Edit Prod Calibration Allows a manual calibration modification A WARNING screen will then be displayed press ENTER to continue to change Meter Calibration Value...

Page 22: ...nge Volume Unit Once the Totalizer has been changed the display will prompt you to change the Unit of Measure for the Totalizer Highlight the Unit of Measure and press ENTER 4 TEMP PROBE This function...

Page 23: ...Countries or States 8 RESET TOTALISERS System and Product Totalizers record the amount of all liquid that has passed through the meter by product Please Note Resetting the Totalizers will reset the TC...

Page 24: ...level to a specific amount Filling up the inventory to 100 Tank Capacity Emptying the Inventory to 0 Can be done during a Shift VIEW INVENTORY Allows you to see your total inventory levels of numerou...

Page 25: ...1 Type and press ENTER TAX 1 VALUE Highlight Tax 1 Value and press ENTER Input tax value and press ENTER TAX 2 NAME Highlight Tax 2 Name and press ENTER Input tax name and press ENTER TAX 2 TYPE High...

Page 26: ...S2 slow flow valves Semi Auto Semi Automatic tune preset shutoff for Solenoid S2 slow flow valve Highlight Semi Auto and press ENTER Input Solenoid S1 fast flow valve closure and press ENTER Next Fix...

Page 27: ...g a factory supplied USB cable attach the thumb drive to the USB port closest to the inside of the register This port is the highest on the circuit board of the two See Figure 1 3 Plug the USB cable i...

Page 28: ...CHAIN on the Client Unit To tie the Client to the next Client unit on the Daisy Chain strip a small amount of wire and run the wire from slot A and B of DAISY CHAIN to slot A and B of the next client...

Page 29: ...Register If you are not using the Daisy Chain for the Printer Please Disregard the Enabling and Selecting the Printer Steps Enable the Printer PRINTER SETTINGS ENABLE DISABLE PRINTER ENABLE PRINTER Se...

Page 30: ...IN on the Client Unit To tie the Client to the next Client unit on the Daisy Chain strip a small amount of wire and run the wire from slot A and B of DAISY CHAIN to slot A and B of the next client s D...

Page 31: ...Select the Printer PRINTER SETTINGS SELECT PRINTER REMOTE ENABLE SYSTEM SETTINGS CONNECTIVITY SETTINGS NETWORK SETTINGS ADDRESS DEVICE ADDRESS Select the number of the unit you are using ex 2 if it i...

Page 32: ...f Lading Once you have finished in Inventory select STOP CANCEL ENTER BILL Nr START ENTER Add Inventory While holding Shift select Mode System Menu Product Settings Inventory Add Inventory GIVE INVENT...

Page 33: ...ect START ENTER Use the arrow keys to highlight your product Select START ENTER Use the arrow keys to highlight TEMP PROBE select START ENTER Selecting TEMP PROBE will take you to Offset Calibration P...

Page 34: ...he start of a delivery Press the Start Button this energizes the solenoids Allow the pump to pack the hose TCS 3000 Trouble Shooting Guide The TCS3000 troubleshooting guide covers most common problem...

Page 35: ...Check the 7 5A in line fuse for continuity It is located in the accessory power line Replace if necessary 3 If the green light blinks fast it is doing what it is supposed to but then it will go to a s...

Page 36: ...n or shorted cir cuit between RTD probe and the TCS 3000 1 Check the RTD Probe and terminal block for continuity 2 Remove terminal block Temp Probe from the circuit board On the terminal block measure...

Page 37: ...oesn t shut off Valve was never set up or calibrated Select the product and calibrated the valve for zero shutoff Display is read ing in reverse Channel A and B are wired backwards Switch wiring betwe...

Page 38: ...Product Configuration may result in the TCS3000 to not function correctly 2 Products that have been calibrated may appear either as an Active or Inactive Product The TCS 3000 must have at least 1 Acti...

Page 39: ...discovery of a purported breach of warranty but not later than the expiration of the warranty period Once authorization is received return the defective meter piece of equipment or component covered b...

Page 40: ...2515 Charleston Place Fort Wayne IN 46808 Toll Free 800 348 4753 Phone 260 484 0382 Fax 260 484 9230 Email sales tcsmeters com Website www tcsmeters com TCS900040...

Reviews: