33
Parameter
Settings Option
Code
Breaker Type
ISM15_Shell_2
3
Undervoltage
UV On
0
UV Off
1
UV Delay
Undervoltage delay (0 - 60 s)
0 - 60
UV Reclosing
Reclosing trips to lockout
1
2
UV Reclosing Delay
Reclosing Delay (15 - 60 s)
15 - 60
Digital Output 1
Disabled
1
Close / Open Position
2
Loss of Supply
3
Driver Ready
4
Malfunction
5
Digital Output 2
Disabled
1
Close / Open Position
2
Loss of Supply
3
Driver Ready
4
Malfunction
5
Digital Output 3
Disabled
1
Close / Open Position
2
Loss of Supply
3
Driver Ready
4
Malfunction
5
Trip Delay
Trip delay (4 - 40 ms)
4 - 40
Close Delay
Close delay (4 - 40 ms)
4 - 40
Trip Input
By closing the contact
1
By opening the contact
2
Close Input
By closing the contact
1
By opening the contact
2
Example
For a control module programmed with breaker type ISM15_Shell_2, UV on, UV delay of zero seconds, 1 trip to lockout with 60
second reclosing delay, DO1 = Close / Open Position, DO2 = Driver Ready, DO3 = Malfunction, trip delay of 12ms, close delay
of 12ms, trip input = By opening the contact, close input = By opening the contact:
Settings code = 3-10-160-245-1212-21
Trip and / or close delays below 12ms will ship with an HS suffix model code. For example the CM_16_1 with 4ms trip delay for
120VAC operation will ship with model code CM_16_1(220HS).
Pre-Programmed Settings Code Designations Table
3
Summary of Contents for ISM Shell_2 Series
Page 2: ...2...
Page 6: ...6 1 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 7: ...7 Introduction 1...
Page 12: ...12 1 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 13: ...13 Receiving Handling and Storage 2...
Page 19: ...19 Ins tallation 3...
Page 36: ...36 3 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 37: ...37 Switching and Control Functions 4...
Page 41: ...41 Commiss ioning Maintenance 5...
Page 44: ...44 5 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 45: ...45 Signalling 6...
Page 49: ...49 Special Applications Fast Switching 6...
Page 53: ...53 Product Line 7...
Page 55: ...55 Dimens ions and Weights 8...
Page 61: ...61 8 Mating part with interlocking lever Interlockingshaftwithmountedinterlockinglever...
Page 62: ...62 Circuit Diagrams 9...
Page 63: ...63 ISM15_Shell_2 with CM_1501_01 9...
Page 64: ...64 ISM15_Shell_2 with CM_16_1 9...
Page 65: ...65 9 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 66: ...66 Technical Data 10...
Page 71: ...71 10 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 72: ...72 Regulations and Ambient Conditions 11...
Page 74: ...74 Legal Information 12...
Page 77: ...77 12 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...79 Date 12...
Page 80: ...80 Date 12...
Page 81: ...81 Date 12...