ISM Forced Trip by an Undervoltage Relay (Optional - CM_1501
Series)
In cases where the ISM is required to trip when the auxiliary power supply voltage drops below the minimum value
an additional undervoltage relay is required (not part of the scope of supply). The trip contact of the undervoltage
relay shall be integrated into the dry contact trip command circuit of the CM. If the CM was ready for operation
before the voltage dropped below the minimum value, tripping of the ISM is possible within 30 s after the voltage
dropped below the minimum level.
Note that for undervoltage trip functions it is recommended to use the CM_16 series where possible due to the
more flexible capability it provides for reclosing and UV trip delay.
Output to Magnetic Actuator and Input for ISM Pos ition
Indication
The cables between the ISM and CMnas well as the coils of the magnetic actuator are monitored permanently (see
malfunction indication table, page 43). Internally at the auxiliary switch inputs of the CM_1501 230 V DC is applied
for the ISM auxiliary switch S13. The CM_16 series does not utilize the auxiliary switch; instead the impedence of
the actuator coils is monitored for position of the breaker as well as loss of connection.
Operations Counter
Depending on site or switchgear requirements, a method of recording circuit breaker close / open operations may
be needed. The preferred method of tracking operations is to utilize the breaker wear monitor available on most
modern didgitical relays, which will calculate the remaining lifetime based on number of operations and switching
interruptions. Alternatively, a pulse counter per the table below can be ordered from Tavrida that will indicate the
number of mechanical operations. These counters can be wired to any of the 52a auxiliary contacts on the breaker.
Auxiliary Voltage
Pulse Counter Part Number
24VDC
5RSI62.2 24C
48VDC
5RSI62.2 48C
120VAC
5RSI62.2 110
125VDC
5RSI62.2 110C
220VAC
5RSI62.2 220
Summary of Contents for ISM Shell_2 Series
Page 2: ...2...
Page 6: ...6 1 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 7: ...7 Introduction 1...
Page 12: ...12 1 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 13: ...13 Receiving Handling and Storage 2...
Page 19: ...19 Ins tallation 3...
Page 36: ...36 3 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 37: ...37 Switching and Control Functions 4...
Page 41: ...41 Commiss ioning Maintenance 5...
Page 44: ...44 5 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 45: ...45 Signalling 6...
Page 49: ...49 Special Applications Fast Switching 6...
Page 53: ...53 Product Line 7...
Page 55: ...55 Dimens ions and Weights 8...
Page 61: ...61 8 Mating part with interlocking lever Interlockingshaftwithmountedinterlockinglever...
Page 62: ...62 Circuit Diagrams 9...
Page 63: ...63 ISM15_Shell_2 with CM_1501_01 9...
Page 64: ...64 ISM15_Shell_2 with CM_16_1 9...
Page 65: ...65 9 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 66: ...66 Technical Data 10...
Page 71: ...71 10 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 72: ...72 Regulations and Ambient Conditions 11...
Page 74: ...74 Legal Information 12...
Page 77: ...77 12 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...79 Date 12...
Page 80: ...80 Date 12...
Page 81: ...81 Date 12...