CNG dispensers TATSUNO EUROPE ‐ Quick User Guide   

 

 

21

The most frequent delivery termination is during filling the full 
storage tank when the gas flow rate drops under the set value 
(4)  at  dispensers  without  temperature  compensation  and 
delivery termination by attaining the maximum possible gas 
mass  calculated  by  temperature  compensation  (5).  In  both 
cases delivery termination is signalled by the “FULL” message 
on the product unit price display. 

Delivery  is  finished  by  hanging  the  delivery  nozzle  to  the 
dispenser. 

NOTE

 

Delivery  with  temperature  compensationis  performed  so  that  the  dispenser  shall  verify  the 

situation  in  the  vehicle  storage  tank  by  a  small  amount  of  gas  at  the  beginning  of  delivery  and 
calculates the maximum gas mass which it is able to deliver under given ambient temperature. After 
attaining the maximum mass, it finishes the delivery and shows the “FULL” message. According to 
technical rules of TPG 304 02 art. 4.5.4 the limit values in the Czech Republic for calculating maximum 
gas mass in the vehicle are as follows: 

a) maximum gas pressure converted to 15 °C – 20.0 MPa 
b) attain maximum overpressure in a vehicle 26.5 MPa  
c) attaining maximum gas temperature in a vehicle 82 °C

 

 

 

NOTE

 

According  to  ISO/DIS  16923,  par.  7.5  CNG  dispensers  must  be  equipped  with  a  breakaway  coupling 

located between the delivery nozzle and the dispenser. This breakaway coupling disconnects the gas flow rate 
at both ends in case of emergency. The force that causes breaking the coupling must be higher than 220N and 
lower than 600N.  CNG dispensers are standardly equipped with a breakaway coupling with a magnetic sensor 
of breaking. After breaking the hose the delivery is immediately terminated (magnetic valves are closed) and the 
display shows the error message E67.

 

 

RESPONSIBILITIES OF CNG DISPENSER ATTENDANTS 

 

Observe operating rules and regulations and operating instructions of gas devices.

 

 

Keep the operated devices in a safe and proper condition. 

 

Immediately inform the operator about each defect, failure or abnormality during operation. 

 

Immediately decommission the device in case of gas leak or danger. 

 

Keep tidiness and cleanliness and ensure that no unauthorized persons are nearby the device. 

 

Inform the operator about circumstances that impede the device operation for the attendant. 

 

Properly write records to the log book about the shift start and finish, inspections, repairs and audits. 

 

The dispenser and reservoir attendant must not perform any repairs or change the device and safety fittings 
setting on his/her own.

 

 

Regularly check the condition of delivery hoses, their correct position in the dispenser and protect then from 
damage.

 

 

406

.

1

15

.

326

Kg

 

€/kg

 

FULL

Summary of Contents for CNG050

Page 1: ...sersUserRev00 docx Revision Date Revision 00 September 2018 Number of pages 35 including cover Created by Ing Milan Berka TATSUNO EUROPE a s Pra sk 2325 68 678 01 Blansko Czech Republic tel 420 516 42...

Page 2: ...01 Blansko Czech Republic Tel 420 516428411 Fax 420 516428410 e mail info tatsuno europe com http www tatsuno europe com Copyright Neither the manual nor any part of it may be reproduced without the e...

Page 3: ...1 15 ERROR statistics code 13 17 2 1 16 Current operating temperature code 14 17 2 1 17 Resetting daily totalizers code 15 17 3 OPERATION 18 3 1 INSTRUCTIONS FOR SAFE OPERATION 18 3 2 DISPENSER COMMIS...

Page 4: ...secorrespondstoreality The manufacturerreservestheright to alter the technical specifications of the device or its properties without a written notice due to its development and continuous improvement...

Page 5: ...ertified components made of stainless steel or galvanized steel The access to the CNG pressure system is fitted with a lever closable ball valve then 25 m input particle filters to protect pressure co...

Page 6: ...a 2 0 Maximum delivering gas pressure Pv MPa 20 0 15 C 26 5 Maximum unit price number of digits 9999 4 Maximum amount to pay number of digits 999999 6 Scale interval kg 0 01 or 0 001 Display type Elec...

Page 7: ...nser concerns SUNNY EX EURO and SHARK ECONOMY the location of the nameplate which is always closest to product No 1 and nozzle No 1 1A is decisive In the case of a double sided dispenser the right sid...

Page 8: ...managers and this remote controller allows them to perform reading non resettable electronic mass totalizers of all delivery hoses reading and resetting daily electronic mass and financial totalizers...

Page 9: ...CNG dispensers TATSUNO EUROPE Quick User Guide 9 Figure 2 Minimum active range of the dispenser remote controller Figure 3 Description of keys of the manager remote controller PDERT 5O...

Page 10: ...at the dispenser display from the distance of approx 1m from the dispenser display centre and pressing the A button All delivery nozzles on the dispenser must be hung in advance and the sale on the di...

Page 11: ...splay shows the value of the first parameter 01 Now it is possible to browse parameters by using the key or by entering the number of searched parameter and confirm with the ENT key to go directly to...

Page 12: ...ment of their last resetting Table 5 Description of values of P02 parameter Parameter Meaning P02 1 amount of gas flown through the hose 1 in hundredths of kilogram x 0 01kg P02 2 amount of gas flown...

Page 13: ...seconds the P04 2 parameter shows and sets date in the DDMMYY format day month year example 15 35 11 24 12 2011 Setting is made by pressing the Ent key and entering the time date in the correct format...

Page 14: ...g 30 E30 zero fuel unit price After pressing the ENT key the display shows time and date of defect occurrence 12 45 10 31 12 2016 shown in the figure After pressing the key the display shows the code...

Page 15: ...History of last deliveries P07 Parameter Meaning P7 00 last delivery of the dispenser the latests P7 01 last but one delivery of the dispenser P7 49 49th delivery of the dispenser P7 50 50th delivery...

Page 16: ...he main displaying unit master display P10 3 Serial number of the auxiliary displaying unit slave display P10 4 Serial number of the unit of electromechanical totalizers P10 5 Serial number of the hea...

Page 17: ...from dispenser commissioning or from resetting the statistics by the service engineer 2x You can browse the error statistics by using or keys 2 1 16 CURRENT OPERATING TEMPERATURE CODE 14 This function...

Page 18: ...he dispenser is equipped with the STOP button for emergencies The procedure in case of fire or emergency is precisely defined in local operating rules and regulations the attendant must be demonstrabl...

Page 19: ...the last data that was on the display before the last display switching off Now the dispenser is ready for delivery If the dispenser works in the manual mode it is then possible to immediately start...

Page 20: ...and the pressure storage tank of the vehicle is filled with compressed natural gas At the moment whenthedeliveryspeeddecreasesunderthedefinedlimit the electronic counter automatically switches delive...

Page 21: ...5 CNG dispensers must be equipped with a breakaway coupling located between the delivery nozzle and the dispenser This breakaway coupling disconnects the gas flow rate at both ends in case of emergen...

Page 22: ...ble to protect your hands by wearing gloves and wear safety goggles 3 4 1 ELECTROMECHANICAL TOTALIZERS On demand TATSUNO EUROPE dispensers are equipped with electromechanical totalizers for monitoring...

Page 23: ...witch from the automatic to the manual mode By default the dispensers are connected and set as it is expected they should work at the fuel station i e if the fuel station is equipped with a control sy...

Page 24: ...re setting the quantity The customer arrives to the dispenser and wants to refill 20 kilograms of gas The dispenser attendant pre sets the value 20 by using the pre set keypad presses the 10 kg button...

Page 25: ...STOP command has been received from the booth after the preset number preset amount has been reached or after the allowed time without delivery has been exceeded Fault signalling or maintenance requir...

Page 26: ...DISPENSER IS OBLIGED TO Appoint an employee responsible for the operation and technical condition of the dispenser Ensure inspections testing repairs and maintenance in a professional way Register do...

Page 27: ...esign parts car cosmetics Recommended maintenance of stainless covers Wash them with warm water at least twice per month according to the level of fouling At least once a month or after each higher su...

Page 28: ...employee of the authorized service company 4 1 5 DISCHARGE NEEDLE VALVE It is located in such parts of the pressure module from which the media must be discharged in case on maintenance or service NVx...

Page 29: ...on hose with an internal diameter of 6 4 mm is intended for transporting residual gas from the neck area of the delivery nozzle Both hoses are supplied in a standard length of 3M At one side they end...

Page 30: ...o valves that prevent gas from leaking from both ends of the breakaway coupling after its disconnecting Breakaway couplings used at OCEAN CNG dispensers allow up to 100 repetitive disconnections and c...

Page 31: ...hange the dispenser mode from automatic to manual see chapters 2 1 14 or Chyba Nenalezen zdroj odkaz If the stand is in a manual mode there is a fault on the control computer side An error message E18...

Page 32: ...ent and impurities in the inlet pipeline and pressure system of the dispenser During operation it is necessary to regularly check water and impurities presence and perform cleaning if necessary 4 3 2...

Page 33: ...CNG dispensers TATSUNO EUROPE Quick User Guide 33 NOTES...

Reviews: