CNG dispensers TATSUNO EUROPE ‐ Quick User Guide   

 

 

31

4.2.

 

TROUBLESHOOTING AND SOLVING DISPENSER DEFECTS 

When you encounter a problem, first read the 

"What to do if ..." table

 (see Table 16) where the most frequently 

asked questions of the dispenser users about the problems encountered at the fuel station are described. 

In the event of a dispenser defect, the electronic counter that controls the dispenser displays a fault message in 
the form of a numeric code.  

Table 16 ‐ What to do if ... 

The dispenser does not respond to the removal of the delivery nozzle and there is no fault message on the display 
This  means  that  the  dispenser  is  without  the  power  supply,  or  the  delivery  nozzle  on  the  dispenser  is  poorly 
hinged, or that the dispenser is blocked by the control system.  
 

 

Check proper hanging of all delivery nozzles 

 

Check whether pumping made on the dispenser is paid at the cash desk 

 

If the dispenser is in manual mode, try unlock the dispenser with the IR remote controller (press the "0")

 

Turn the power supply of dispenser counter off and on.  

 

Check the power supply of dispenser, i.e. when the power is turned on the display must pass the test 

 

Check the position of the circuit‐breaker for the single‐phase power supply 230V of the dispenser in the 
main switchboard of the fuel station  

 

If the dispenser is connected to the control computer, the dispenser blocking may be coupled to a control 
system  that  does  not  release  the  dispenser  for  pumping  or  blocks  the  dispenser.  Turn  the  power 
dispenser off and on and change the dispenser mode from automatic to manual – see chapters 2.1.14 or 

Chyba!  Nenalezen  zdroj  odkazů.

.  If  the  stand  is  in  a  manual  mode,  there  is  a  fault  on  the  control 

computer side. 
 

An error message "

E18

” will appear on the display of the dispenser 

This is a dispenser fault message that indicates that communication between the dispenser and the control unit 
(computer, station controller, control console, etc.) has been lost.  

 

check the correct operation of the control unit (turning on the counter, turning on the data converter)  

 

check the data cable connection 
 

After picking up the delivery nozzle an error message 

"E30"

 appears on the display of the dispenser .  

This is a fuel dispenser failure report that states that the fuel unit price is zero.

 

If the rack is operating in a manual mode without the remote control, then the unit price is incorrectly 
set. Set the fuel unit price, see chapter 2.1.6 and 

Chyba! Nenalezen zdroj odkazů.

.

 

 

If the dispenser is controlled remotely, then check the fuel unit price settings in the station controller 
(computer, controller).  Before each delivery, the fuel price is automatically sent to the dispenser. 

 

4.3.

 

SERVICE OF DISPENSERS 

 

 

service work is carried out in accordance with the operating rules at the fuel station 

 

before starting the service, the dispenser must be shut down, marked visibly with the "OUT OF 
SERVICE" sign and the driveway must be marked with the "NO ENTRY” sign 

 

the dispenser must be disconnected from the power supply (switch off by the main switch on 
the switchboard) 

 

the valves on the supply line must be fully closed 

 

during service work, vehicles must be prevented from passing within 5 meters around  

 

a fire extinguisher must be available to workers 

Summary of Contents for CNG050

Page 1: ...sersUserRev00 docx Revision Date Revision 00 September 2018 Number of pages 35 including cover Created by Ing Milan Berka TATSUNO EUROPE a s Pra sk 2325 68 678 01 Blansko Czech Republic tel 420 516 42...

Page 2: ...01 Blansko Czech Republic Tel 420 516428411 Fax 420 516428410 e mail info tatsuno europe com http www tatsuno europe com Copyright Neither the manual nor any part of it may be reproduced without the e...

Page 3: ...1 15 ERROR statistics code 13 17 2 1 16 Current operating temperature code 14 17 2 1 17 Resetting daily totalizers code 15 17 3 OPERATION 18 3 1 INSTRUCTIONS FOR SAFE OPERATION 18 3 2 DISPENSER COMMIS...

Page 4: ...secorrespondstoreality The manufacturerreservestheright to alter the technical specifications of the device or its properties without a written notice due to its development and continuous improvement...

Page 5: ...ertified components made of stainless steel or galvanized steel The access to the CNG pressure system is fitted with a lever closable ball valve then 25 m input particle filters to protect pressure co...

Page 6: ...a 2 0 Maximum delivering gas pressure Pv MPa 20 0 15 C 26 5 Maximum unit price number of digits 9999 4 Maximum amount to pay number of digits 999999 6 Scale interval kg 0 01 or 0 001 Display type Elec...

Page 7: ...nser concerns SUNNY EX EURO and SHARK ECONOMY the location of the nameplate which is always closest to product No 1 and nozzle No 1 1A is decisive In the case of a double sided dispenser the right sid...

Page 8: ...managers and this remote controller allows them to perform reading non resettable electronic mass totalizers of all delivery hoses reading and resetting daily electronic mass and financial totalizers...

Page 9: ...CNG dispensers TATSUNO EUROPE Quick User Guide 9 Figure 2 Minimum active range of the dispenser remote controller Figure 3 Description of keys of the manager remote controller PDERT 5O...

Page 10: ...at the dispenser display from the distance of approx 1m from the dispenser display centre and pressing the A button All delivery nozzles on the dispenser must be hung in advance and the sale on the di...

Page 11: ...splay shows the value of the first parameter 01 Now it is possible to browse parameters by using the key or by entering the number of searched parameter and confirm with the ENT key to go directly to...

Page 12: ...ment of their last resetting Table 5 Description of values of P02 parameter Parameter Meaning P02 1 amount of gas flown through the hose 1 in hundredths of kilogram x 0 01kg P02 2 amount of gas flown...

Page 13: ...seconds the P04 2 parameter shows and sets date in the DDMMYY format day month year example 15 35 11 24 12 2011 Setting is made by pressing the Ent key and entering the time date in the correct format...

Page 14: ...g 30 E30 zero fuel unit price After pressing the ENT key the display shows time and date of defect occurrence 12 45 10 31 12 2016 shown in the figure After pressing the key the display shows the code...

Page 15: ...History of last deliveries P07 Parameter Meaning P7 00 last delivery of the dispenser the latests P7 01 last but one delivery of the dispenser P7 49 49th delivery of the dispenser P7 50 50th delivery...

Page 16: ...he main displaying unit master display P10 3 Serial number of the auxiliary displaying unit slave display P10 4 Serial number of the unit of electromechanical totalizers P10 5 Serial number of the hea...

Page 17: ...from dispenser commissioning or from resetting the statistics by the service engineer 2x You can browse the error statistics by using or keys 2 1 16 CURRENT OPERATING TEMPERATURE CODE 14 This function...

Page 18: ...he dispenser is equipped with the STOP button for emergencies The procedure in case of fire or emergency is precisely defined in local operating rules and regulations the attendant must be demonstrabl...

Page 19: ...the last data that was on the display before the last display switching off Now the dispenser is ready for delivery If the dispenser works in the manual mode it is then possible to immediately start...

Page 20: ...and the pressure storage tank of the vehicle is filled with compressed natural gas At the moment whenthedeliveryspeeddecreasesunderthedefinedlimit the electronic counter automatically switches delive...

Page 21: ...5 CNG dispensers must be equipped with a breakaway coupling located between the delivery nozzle and the dispenser This breakaway coupling disconnects the gas flow rate at both ends in case of emergen...

Page 22: ...ble to protect your hands by wearing gloves and wear safety goggles 3 4 1 ELECTROMECHANICAL TOTALIZERS On demand TATSUNO EUROPE dispensers are equipped with electromechanical totalizers for monitoring...

Page 23: ...witch from the automatic to the manual mode By default the dispensers are connected and set as it is expected they should work at the fuel station i e if the fuel station is equipped with a control sy...

Page 24: ...re setting the quantity The customer arrives to the dispenser and wants to refill 20 kilograms of gas The dispenser attendant pre sets the value 20 by using the pre set keypad presses the 10 kg button...

Page 25: ...STOP command has been received from the booth after the preset number preset amount has been reached or after the allowed time without delivery has been exceeded Fault signalling or maintenance requir...

Page 26: ...DISPENSER IS OBLIGED TO Appoint an employee responsible for the operation and technical condition of the dispenser Ensure inspections testing repairs and maintenance in a professional way Register do...

Page 27: ...esign parts car cosmetics Recommended maintenance of stainless covers Wash them with warm water at least twice per month according to the level of fouling At least once a month or after each higher su...

Page 28: ...employee of the authorized service company 4 1 5 DISCHARGE NEEDLE VALVE It is located in such parts of the pressure module from which the media must be discharged in case on maintenance or service NVx...

Page 29: ...on hose with an internal diameter of 6 4 mm is intended for transporting residual gas from the neck area of the delivery nozzle Both hoses are supplied in a standard length of 3M At one side they end...

Page 30: ...o valves that prevent gas from leaking from both ends of the breakaway coupling after its disconnecting Breakaway couplings used at OCEAN CNG dispensers allow up to 100 repetitive disconnections and c...

Page 31: ...hange the dispenser mode from automatic to manual see chapters 2 1 14 or Chyba Nenalezen zdroj odkaz If the stand is in a manual mode there is a fault on the control computer side An error message E18...

Page 32: ...ent and impurities in the inlet pipeline and pressure system of the dispenser During operation it is necessary to regularly check water and impurities presence and perform cleaning if necessary 4 3 2...

Page 33: ...CNG dispensers TATSUNO EUROPE Quick User Guide 33 NOTES...

Reviews: