background image

TATSUNO  EUROPE a.s., www.tatsuno‐europe.com 

 

 

30

not repairable. In case of its defect it is replaced. Replacement may only be performed by an employee of the 
authorized service company. 

 

It is necessary to visually check mechanical wear of the end piece and check its tightness by using a 
foaming agent at least 

once a month.

 The damaged filling end piece must be immediately replaced! 

Replacement may only be performed by an employee of the authorized service company. 

 

We recommend lubricating the fastening mechanism of the end piece neck with silicon oil 

once per 3 

months.

 This activity may be performed by the fuel station attendant. 

 

It is necessary to check conductivity of the breakaway coupling‐hose‐end piece set at least 

once per 6 

months

 – i.e. resistance between the end of the filling end piece and the central grounding terminal of 

the dispenser must be lower than 1 MΩ (testing voltage of 500V) in a pressurized operating condition 
and without pressure. 

4.1.12.

 

SAFETY DISCONNECTING COUPLING (BREAKAWAY COUPLING)  

The safety disconnecting coupling is intended for disconnecting the filling hose in case of its extreme tensile 
stress. It is fitted with two valves that prevent gas from leaking from both ends of the 
breakaway coupling after its disconnecting. Breakaway couplings used at OCEAN CNG 
dispensers allow up to 100 repetitive disconnections and connections. Connection may 
only be performed by an employee of the authorized service company by using a special 
tool. 

 

It is necessary to visually check mechanical wear of the breakaway coupling and check its tightness by 
using a foaming agent at least 

once a month.

 The damaged breakaway coupling must be immediately 

replaced! Replacement may only be performed by an employee of the authorized service company. 

 

It is necessary to check conductivity of the breakaway coupling‐hose‐end piece set at least 

once per 6 

months

 – i.e. resistance between the end of the filling end piece and the central grounding terminal of 

the dispenser must be lower than 1 MΩ (testing voltage of 500V) in a pressurized operating condition 
and without pressure. 

Table 15 ‐ Maintenance intervals ( ISO/DIS 16923) 

Maintenance activity 

weekly 

monthly 

6 months 

Inspection of filling end piece damage 

 

 

Inspection of hose damage 

 

 

Visual inspection of the breakaway coupling 

 

 

Tightness test of the filling end piece 

 

 

Tightness test of the breakaway coupling 

 

 

Tightness test of pipeline systems and threaded joints 

 

 

Conductivity test of the set of breakaway coupling‐hose‐end piece 

 

 

 

 

 

Summary of Contents for CNG050

Page 1: ...sersUserRev00 docx Revision Date Revision 00 September 2018 Number of pages 35 including cover Created by Ing Milan Berka TATSUNO EUROPE a s Pra sk 2325 68 678 01 Blansko Czech Republic tel 420 516 42...

Page 2: ...01 Blansko Czech Republic Tel 420 516428411 Fax 420 516428410 e mail info tatsuno europe com http www tatsuno europe com Copyright Neither the manual nor any part of it may be reproduced without the e...

Page 3: ...1 15 ERROR statistics code 13 17 2 1 16 Current operating temperature code 14 17 2 1 17 Resetting daily totalizers code 15 17 3 OPERATION 18 3 1 INSTRUCTIONS FOR SAFE OPERATION 18 3 2 DISPENSER COMMIS...

Page 4: ...secorrespondstoreality The manufacturerreservestheright to alter the technical specifications of the device or its properties without a written notice due to its development and continuous improvement...

Page 5: ...ertified components made of stainless steel or galvanized steel The access to the CNG pressure system is fitted with a lever closable ball valve then 25 m input particle filters to protect pressure co...

Page 6: ...a 2 0 Maximum delivering gas pressure Pv MPa 20 0 15 C 26 5 Maximum unit price number of digits 9999 4 Maximum amount to pay number of digits 999999 6 Scale interval kg 0 01 or 0 001 Display type Elec...

Page 7: ...nser concerns SUNNY EX EURO and SHARK ECONOMY the location of the nameplate which is always closest to product No 1 and nozzle No 1 1A is decisive In the case of a double sided dispenser the right sid...

Page 8: ...managers and this remote controller allows them to perform reading non resettable electronic mass totalizers of all delivery hoses reading and resetting daily electronic mass and financial totalizers...

Page 9: ...CNG dispensers TATSUNO EUROPE Quick User Guide 9 Figure 2 Minimum active range of the dispenser remote controller Figure 3 Description of keys of the manager remote controller PDERT 5O...

Page 10: ...at the dispenser display from the distance of approx 1m from the dispenser display centre and pressing the A button All delivery nozzles on the dispenser must be hung in advance and the sale on the di...

Page 11: ...splay shows the value of the first parameter 01 Now it is possible to browse parameters by using the key or by entering the number of searched parameter and confirm with the ENT key to go directly to...

Page 12: ...ment of their last resetting Table 5 Description of values of P02 parameter Parameter Meaning P02 1 amount of gas flown through the hose 1 in hundredths of kilogram x 0 01kg P02 2 amount of gas flown...

Page 13: ...seconds the P04 2 parameter shows and sets date in the DDMMYY format day month year example 15 35 11 24 12 2011 Setting is made by pressing the Ent key and entering the time date in the correct format...

Page 14: ...g 30 E30 zero fuel unit price After pressing the ENT key the display shows time and date of defect occurrence 12 45 10 31 12 2016 shown in the figure After pressing the key the display shows the code...

Page 15: ...History of last deliveries P07 Parameter Meaning P7 00 last delivery of the dispenser the latests P7 01 last but one delivery of the dispenser P7 49 49th delivery of the dispenser P7 50 50th delivery...

Page 16: ...he main displaying unit master display P10 3 Serial number of the auxiliary displaying unit slave display P10 4 Serial number of the unit of electromechanical totalizers P10 5 Serial number of the hea...

Page 17: ...from dispenser commissioning or from resetting the statistics by the service engineer 2x You can browse the error statistics by using or keys 2 1 16 CURRENT OPERATING TEMPERATURE CODE 14 This function...

Page 18: ...he dispenser is equipped with the STOP button for emergencies The procedure in case of fire or emergency is precisely defined in local operating rules and regulations the attendant must be demonstrabl...

Page 19: ...the last data that was on the display before the last display switching off Now the dispenser is ready for delivery If the dispenser works in the manual mode it is then possible to immediately start...

Page 20: ...and the pressure storage tank of the vehicle is filled with compressed natural gas At the moment whenthedeliveryspeeddecreasesunderthedefinedlimit the electronic counter automatically switches delive...

Page 21: ...5 CNG dispensers must be equipped with a breakaway coupling located between the delivery nozzle and the dispenser This breakaway coupling disconnects the gas flow rate at both ends in case of emergen...

Page 22: ...ble to protect your hands by wearing gloves and wear safety goggles 3 4 1 ELECTROMECHANICAL TOTALIZERS On demand TATSUNO EUROPE dispensers are equipped with electromechanical totalizers for monitoring...

Page 23: ...witch from the automatic to the manual mode By default the dispensers are connected and set as it is expected they should work at the fuel station i e if the fuel station is equipped with a control sy...

Page 24: ...re setting the quantity The customer arrives to the dispenser and wants to refill 20 kilograms of gas The dispenser attendant pre sets the value 20 by using the pre set keypad presses the 10 kg button...

Page 25: ...STOP command has been received from the booth after the preset number preset amount has been reached or after the allowed time without delivery has been exceeded Fault signalling or maintenance requir...

Page 26: ...DISPENSER IS OBLIGED TO Appoint an employee responsible for the operation and technical condition of the dispenser Ensure inspections testing repairs and maintenance in a professional way Register do...

Page 27: ...esign parts car cosmetics Recommended maintenance of stainless covers Wash them with warm water at least twice per month according to the level of fouling At least once a month or after each higher su...

Page 28: ...employee of the authorized service company 4 1 5 DISCHARGE NEEDLE VALVE It is located in such parts of the pressure module from which the media must be discharged in case on maintenance or service NVx...

Page 29: ...on hose with an internal diameter of 6 4 mm is intended for transporting residual gas from the neck area of the delivery nozzle Both hoses are supplied in a standard length of 3M At one side they end...

Page 30: ...o valves that prevent gas from leaking from both ends of the breakaway coupling after its disconnecting Breakaway couplings used at OCEAN CNG dispensers allow up to 100 repetitive disconnections and c...

Page 31: ...hange the dispenser mode from automatic to manual see chapters 2 1 14 or Chyba Nenalezen zdroj odkaz If the stand is in a manual mode there is a fault on the control computer side An error message E18...

Page 32: ...ent and impurities in the inlet pipeline and pressure system of the dispenser During operation it is necessary to regularly check water and impurities presence and perform cleaning if necessary 4 3 2...

Page 33: ...CNG dispensers TATSUNO EUROPE Quick User Guide 33 NOTES...

Reviews: