Connecting the Library to AC Power
3-4
Select one of the following options:
• Connect no more than two libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm
2
<HAR> cord with
minimum 10A plug. Must be three wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord with
three wire IEC60309 rated 16A. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord
permanently wired to the electrical supply.
Must be connected with a three wire cable
and have a ground warning label.
Connect all libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
5-10
Select one of the following options:
• Connect no more than two libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm
2
<HAR> cord with
minimum 10A plug. Must be three wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord with
three wire IEC60309 rated 16A. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord
permanently wired to the electrical supply.
Must be connected with a three wire cable
and have a ground warning label.
Select one of the following options:
• Connect no more than 4 libraries to each
AC distribution unit rated 15A or 20A, with
a minimum 14AWG three wire cord, and a
15A or 20A plug. Must be three wire
grounding plug and wall outlet.
• Connect all libraries to one AC distribution
unit rated 20A, with a minimum 14AWG
three wire cord, with a 20A plug. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 20A, with a minimum
14AWG three wire cord, permanently
wired to the electrical supply and have a
ground warning label.
# of
Library
Modules
Distribution Unit Requirements
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)