Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Connecting the Library to AC Power
41
Connecting the Library to AC Power
0
This section explains how to connect the library to AC power.
M1500 Power
Requirements
0
To connect the M1500 to AC power:
1
, select appropriate AC distribution unit(s) for your
library configuration and input voltage.
2
Connect the power cable (provided in the accessories kit) to the power
inlet on the back of the library (see
) and to the AC distribution
unit.
Figure 38 Power Inlet
Table 7 AC Distribution
Requirements, M1500
Warning:
AC distribution units (power strips) must be certified for
safety by an agency acceptable to the country of use. For
use in the United States and Canada, distribution units
must be UL listed and CSA certified. For use in Europe,
distribution units must be CE marked. National
certifications for other countries depend on local
requirements.
# of
Library
Modules
Distribution Unit Requirements
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
1-2
Connect libraries to one AC distribution unit
rated minimum 10A, minimum 1.00mm
2
<HAR> cord with minimum 10A plug. Must
be three wire grounding plug and wall outlet.
Connect libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Power inlet