Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
22
Installing a Rack Mount Library
9
Tighten the nuts securing the shelves to the shelf extenders.
The shelf installation is now complete. Proceed to
on page 28 to install the library.
Installing the Shelves in a Full U Position
0
To install the rack mount shelves in a full U position:
1
From the five sizes of inserts provided in the rack mount kit, select the
insert type that best fits into the holes in the rack rails. The heads of the
inserts (not the threads) should fit into the holes in the rack rails smoothly
and with very little play.
The insert part numbers are:
• 213468 (for rails with 9 mm square holes)
• 213469 (for rails with 7 mm diameter unthreaded holes)
• 213471 (for rails with M6 threaded holes)
• 213473 (for rails with 10-32 UNF, 12-24 UNC, or M5 threaded holes)
• 213474 (for rails with 1/4 inch diameter unthreaded holes)
These inserts will be screwed into the holes in the front and rear flanges of
the rack mount shelves.
2
Screw three inserts into the front flange of each rack mount shelf in
positions 1, 4, and 8 (counting from the bottom up, with 1 being the
lowest hole) (see
).
Note:
The universal rack mount kit contains screws and nuts for
many different types of rack. You will have many of these
screws and nuts left over after installing the rack mount
shelves and library.
Note:
The middle library in a 3-high M2500 stack is mounted in a full U
position.
Note:
Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.