TAC Xenta 400 I/O modules
4 Installation
If a shielded communication cable is used, the shield must be grounded
at one point only.
Redundant wires (second pair of Siemens J-Y(st)Y) are cut at the
end of the shield.
Connecting the communication cable
TAC Xenta 1
C1 C2
C1 C2
C1 C2
C1 C2
TAC Xenta 1
TAC Xenta 2
TAC Xenta 2
470 k
Ω
¼ W
Shield is grounded
at one point only
Terminals for
incoming cables
Terminals for
incoming cables
Separate
junction
Communication cable,
unshielded
Communication cable,
shielded