10 (36), 0-004-7771-2 (GB)
TAC AB, 2003-07-01
TAC Xenta 400 I/O modules
2 I/O modules in the TAC Xenta 400 series
The I/O modules are used as expansion modules for the TAC Xenta
controllers, connected to these via the common TP/FT-10 network.
The modules have different I/O configurations to suit different
applications. Some models have indicators for the digital input status
and a manual override for the digital or analog outputs. An overview of
the available models is shown below.
I/O module DI
DI
DO
DO
UI
TI
AO
AO
TAC
status
override
override
Xenta 411
10
-
-
-
-
-
-
-
Xenta 412
10
10
-
-
-
-
-
-
Xenta 421
4
-
5
-
-
-
-
-
Xenta 422
4
4
5
5
-
-
-
-
Xenta 451
-
-
-
-
4
4
2
-
Xenta 452
-
4
1
-
-
4
4
2
2
Xenta 471
-
-
-
-
8
2
-
-
-
Xenta 491
-
-
-
-
-
-
8
-
Xenta 492
-
-
-
-
-
-
8
8
1
Status indication only when the corresponding universal inputs (UI) are being
used as digital inputs.
2
0/4–20 mA or 0/2–10 V DC
where
DI:
Digital input
DO: Digital output
UI:
Universal input
TI:
Thermistor input
AO: Analog output