22 (36), 0-004-7771-2 (GB)
TAC AB, 2003-07-01
TAC Xenta 400 I/O modules
3 Technical description
Type
No.
TAC Menta Block type
Terminal ref.
Override (492)
Analog outputs
8
AO - Analog outputs
Y1 -Y8
– / Man-Auto
Restoring to the default values
If you press the Service Pin for seven seconds during the first minute
following a restart, the parameters of the module will be restored to
the factory default values. A restart occurs following power on.
The green LED on the front will light continuously during activation
(about 7 seconds) and when the restore has finished, it will flash
rapidly (off-line indication).
The parameters of the I/O module will now be restored:
• Domain table index 0: ID len = 1, ID = 11
hex
, Subnet = 1, Node = 1
and Clone Domain = 0.
• Domain table index 1: Unused.
• Address table index 0: Domain = 0, Node = 0, Rpt Tmr = 16,
Retries = 0, Rcv Tmr = 128, Tx Tmr = 16, Subnet = 0.
• Address table index 1: Unused.
• Non_Group_Receive_Timer = 768 ms.
• Node Mode: Unconfig.
• Network Management Authentication = Off
• Pre-emption Timeout = Forever
• The start values of the analog outputs will be reset.
Technical data TAC Xenta 491 and 492
Analog outputs (Y1–Y8):
Quantity ........................................................................................ 8
D/A-resolution ..................................................................... 12 bits
Control voltage .............................................................0–10 V DC
Control current, short-circuit proof .............................. max. 2 mA
Deviation ..........................................................................max ±1%
Manual control of the analog outputs (TAC Xenta 492 only):
Quantity ......................................................................................... 8
Switch positions ......................................................... MAN, AUTO
Control interval .................................................................... 0–10 V
Summary of Contents for Xenta 411
Page 2: ......
Page 6: ...TAC Xenta 400 I O modules Contents 6 36 0 004 7771 2 GB TAC AB 2003 07 01...
Page 32: ...32 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules Index...
Page 34: ...TAC AB 2003 07 01 TAC Xenta 400 I O modules Reply form...
Page 35: ......
Page 36: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 switchboard www tac com...