TAC AB, 2003-07-01
0-004-7771-2 (GB), 21 (36)
TAC Xenta 400 I/O modules
3 Technical description
• Network Management Authentication = Off
• Pre-emption Timeout = Forever
• The inputs will be configured as voltage inputs.
Technical data TAC Xenta 471
Universal inputs (U1–U8):
Quantity ........................................................................................ 8
A/D-resolution ..................................................................... 12 bits
– as current input with an
external
power supply;
Input signal (terminals U–M) ....................................... 0/4–20 mA
Input resistance .................................................................. 20 ohms
accuracy ................................................................. within 0.02 mA
– as current input with an
internal
power supply;
Input signal (terminals 24 V DC–U) ............................... 4–20 mA
Input resistance .................................................................. 20 ohms
accuracy ................................................................. within 0.02 mA
Voltage .................................................................... 24 V DC ±2 V
Current limit, total value .............................................. 200 ±20 mA
– as Voltage input;
Input signal (terminals U–M) ........................... 0–1, 0/2–10 V DC
Input resistance .............................................................. 100 kohms
accuracy .................................................................... within 0.01 V
3.6
The TAC Xenta 491/492 Analog Output module
The modules have eight analog outputs.
Additionally, the TAC Xenta 492 has switches for manually controlling
the analog outputs.
Terminals (491, 492) and switches (492)
TAC Xenta 491/492 terminals and manual control of the TAC Xenta 492
8 Analog outputs:
Manual control
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
G G0 C1C2 Y1 M Y2 M Y3 M
Y4 M Y5 M Y6 M Y7 M Y8 M
AO
~ 0
24 V AC
(19-40 V DC)
}
Comm
}
AO
8 AO
TAC Xenta 492
MAN 1
AUTO
0-10V
MAN 2
AUTO
0-10V
MAN 3
AUTO
0-10V
MAN 4
AUTO
0-10V
MAN 5
AUTO
0-10V
MAN 6
AUTO
0-10V
MAN 7
AUTO
0-10V
MAN 8
AUTO
0-10V
Green LED
Summary of Contents for Xenta 411
Page 2: ......
Page 6: ...TAC Xenta 400 I O modules Contents 6 36 0 004 7771 2 GB TAC AB 2003 07 01...
Page 32: ...32 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules Index...
Page 34: ...TAC AB 2003 07 01 TAC Xenta 400 I O modules Reply form...
Page 35: ......
Page 36: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 switchboard www tac com...