TAC AB, 2003-07-01
0-004-7771-2 (GB), 17 (36)
TAC Xenta 400 I/O modules
3 Technical description
Technical data TAC Xenta 421 and 422
Digital inputs (X1–X4):
Quantity ..........................................................................................4
Voltage across open contact .............................................. 33 V DC
Current through closed contact ................................................4 mA
Pulse input duration (TAC Menta CNT block) ..............min. 20 ms
Digital outputs (K1–K5):
Quantity ........................................................................................... 5
Control voltage, relay outp. protected by a max. 10 A fuse, 230 V AC
Control current .................................................................... max 2 A
Pulse length (TAC Menta DOPU block).......................... min. 0.5 s
LED digital input status indicators (TAC Xenta 422 only):
Quantity ........................................................................................... 4
Color ................................... red or green, selectable via DIP switch
Manual override for digital outputs (TAC Xenta 422 only):
Quantity ..........................................................................................5
Switch positions ................................................... ON, AUTO, OFF
Indicators for Auto output status .................................. green LEDs
Summary of Contents for Xenta 411
Page 2: ......
Page 6: ...TAC Xenta 400 I O modules Contents 6 36 0 004 7771 2 GB TAC AB 2003 07 01...
Page 32: ...32 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules Index...
Page 34: ...TAC AB 2003 07 01 TAC Xenta 400 I O modules Reply form...
Page 35: ......
Page 36: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 switchboard www tac com...