TAC AB, 2003-07-01
0-004-7771-2 (GB), 27 (36)
TAC Xenta 400 I/O modules
4 Installation
TAC Xenta 2
G0
PU
G0
TAC Xenta 1
G0
PU
G0
TR
G0
min 1.5 mm
2
Connections between insulated signal ground rails and the cabinet ground rail
Incoming cables for TAC Xenta 1
Incoming cables for TAC Xenta 2
Insulated signal ground rail
Insulated signal ground rail
Cabinet
ground
rail
Basic circuit diagram for connecting Wall Module ZS 101–105 to TAC Xenta 400 I/O modules
When a Wall Module (ZS101–105) is connected to TAC Xenta 400
I/O modules, the following terminals can be used (term. B2: v 3.0 or
later).
TAC Xenta 45x
Cabinet
terminals
ZS 101-105
G
G0
C2 C1 M
B1
B2
F0 F1 F2 F3 G0 G C2 C1 1 2 3 4 5 6 7 8
0
1
2
3
10 k
Ω
470
Ω
(24 V AC)
min 1.5 mm
2
, max 2 m
230
VAC
G
G0
N
Insulated
signal
ground rail
Cabinet
ground
rail
TAC Xenta 42x
X1
M
K1
KC1
G G0