28 (36), 0-004-7771-2 (GB)
TAC AB, 2003-07-01
TAC Xenta 400 I/O modules
4 Installation
4.2.3 Cables
Power and Communication
G and G0 (Power supply):
G, min. cross-sectional area ............................................... 0.75 mm²
G0 to TAC Xenta, min. cross-sectional area .......................1.5 mm²
C1 and C2 (Network):
The TP/FT-10 system allows the user to wire the control devices
with virtually no topology restrictions.
Min. cross-sectional area ................................ 0.65 mm² (22 AWG)
The max. wire length in one segment depends on the type of wire
and the topology, see the table below.
The wires are not polarity sensitive, but must be a twisted-pair.
For more details, please refer to the ”TAC Xenta Network guide”.
One of the following cable types must be used:
Cable
Max. bus length,
Max. node-to-node
Max. total wire
doubly terminated
distance, single
length single
bus topology (m)
terminated free
terminated free
topology
topology
Belden 85102, single twisted pair
2700
500
500
Belden 8471, single twisted pair
2700
400
500
UL Level IV 22AWG, twisted pair
1400
400
500
Connect-Air 22AWG, 1 or 2 pairs
1400
400
500
Siemens J-Y(st)Y 2x2x0.8
900
320
500
4-wire helical twist, solid, shielded
TIA568A Cat. 5 24AWG, twisted p.
900
250
450
Summary of Contents for Xenta 411
Page 2: ......
Page 6: ...TAC Xenta 400 I O modules Contents 6 36 0 004 7771 2 GB TAC AB 2003 07 01...
Page 32: ...32 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules Index...
Page 34: ...TAC AB 2003 07 01 TAC Xenta 400 I O modules Reply form...
Page 35: ......
Page 36: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 switchboard www tac com...