3060386 | Geniox Air Handling Unit - User Manual
Adjustment and maintenance operations | 41
M.5
Other Components to maintain
M.5.1
The unit
It is very easy to remove inspection doors for access to cleaning,
service, repairs and replacement of components in the unit. Lift
the stainless steel shaft in the hinge to remove the door
The unit should be cleaned once a year when operating with normal air quality for comfort ventilation with no special hygiene require-
ments.
To clean the unit, dry it off with a dry cloth, or use water mixed with a non-corrosive cleaning medium.
Any corrosion — for example the bottom of the section for outdoor air intake and the bottom of the section for exhaust air outlet must
be cleaned off immediately, and the surface treated.
In special operating conditions, where the air is aggressive or very humid, or where there are special hygiene requirements, the unit shall
be cleaned more frequently as required.
Cleaning medium and method should be adapted to the relevant conditions. Any corrosion should be cleaned off immediately, and the
surface treated.
Closing mechanisms are to be lubricated at least once a year. Synthetic door hinges are service free. Seals around inspection doors are
to be cleaned at least once a year and are to be checked for leakage.
It is recommended to treat the seals with a moisture repellent agent.
All seals are to be inspected at least once a year and are to be repaired if necessary.
Grilles for air intake and exhaust air outlet are to be cleaned at least once a year to prevent blockage.
M.5.2
Dampers
Rubber seals between the damper blades and the frame are to
be checked once a year. These seals are not to be lubricated or
treated in any other way.
Summary of Contents for Geniox 10
Page 2: ...Geniox Air Handling Unit User Manual 3060386...
Page 6: ...Geniox Air Handling Unit User Manual 3060386...
Page 35: ...3060386 Geniox Air Handling Unit User Manual Star up adjustments use and commissioning 29...
Page 61: ...3060386 Geniox Air Handling Unit User Manual ERW maintenance 4 8...
Page 62: ...Geniox Air Handling Unit User Manual 3060386 5 1 Roof curb master tables...
Page 63: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 2...
Page 64: ...Geniox Air Handling Unit User Manual 3060386 5 3 Roof curb master tables...
Page 65: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 4...
Page 66: ...Systemair NA 8 Rouse Street Tillsonburg ON N4G 5W8 Toll free 800 688 6363...