3060386 | Geniox Air Handling Unit - User Manual
Information about the residual risks | 33
I.1.5
Filters
I.1.5.1
Risk caused by missing change of filters
Hazards/dangerous area:
• Missing change of filters and missing maintenance decrease the capacity and final consequence will be breakdown.
Dangerous incident:
• By extensive lack of filter change and maintenance the machine can break down.
Claim for reduction of danger:
• In the manual is the method and schedule for change of filters and maintenance specified.
I.1.5.2
Risk caused by the execution of filter change
Hazards/dangerous area:
• Filter panels and filter bags
Dangerous incident:
• To breathe in particles that is harmful to the health.
Claim for reduction of danger:
• Use of particulate respirator – maintenance free including foam face-seal and adjustable pre-threaded headbands (same particulate
respirator as recommended for cleaning of attenuators.
I.1.6
Plug fans
I.1.6.1
Risk caused by lightning strike
Hazards/dangerous area:
• Lightning strike close to the machine.
Dangerous incident:
• Lightning strike can create flash over between phases and conductive parts. This can cause fire or the overvoltage can make injury on
persons
Claim for reduction of danger:
• The installer and user need to be aware of the surge protection devices the unit will require from lightning and equivalent. The type of
surge protection will depend on the location of the unit in the building space.
• Installer and user must take care of this according to local statutory requirements.
I.1.6.2
Risk of rotating impeller caused by stack effect (chimney effect).
Hazards/dangerous area:
• On special occasions stack effect – also called chimney effect – in the ducts create airflows that drives the impellers by turned off
motors.
Dangerous incident:
• Injury of fingers, hands and arms.
Claim for reduction of danger:
• Eliminate this airflow for supply air and exhaust air by dampers with spring return motors for automatic closing of the dampers by
turned off fan motors and by power failure.
Summary of Contents for Geniox 10
Page 2: ...Geniox Air Handling Unit User Manual 3060386...
Page 6: ...Geniox Air Handling Unit User Manual 3060386...
Page 35: ...3060386 Geniox Air Handling Unit User Manual Star up adjustments use and commissioning 29...
Page 61: ...3060386 Geniox Air Handling Unit User Manual ERW maintenance 4 8...
Page 62: ...Geniox Air Handling Unit User Manual 3060386 5 1 Roof curb master tables...
Page 63: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 2...
Page 64: ...Geniox Air Handling Unit User Manual 3060386 5 3 Roof curb master tables...
Page 65: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 4...
Page 66: ...Systemair NA 8 Rouse Street Tillsonburg ON N4G 5W8 Toll free 800 688 6363...