Geniox Air Handling Unit - User Manual | 3060386
G.1.4
Pre-assembly storage
The AHU must be protected from the weather and accidental impact. Plastic packaging
must
be removed and the unit covered with
tarpaulin or similar materials. In order to minimize condensation, sufficient air circulation must be ensured between the covering and the
unit.
G.2
Installation - mechanical
G.2.1
Service area in front of the unit
Important
The unit should be installed in such a way that, there is enough clearance for routine maintenance and inspection
activities. Refer to figure below for service clearance requirements for various Geniox sizes. Enough clearance space
on the access side of the unit is vital for some regular maintenance activities that include: filter replacement, drain pan
inspection and cleaning, Variable Frequency Drive setting, etc. If the unit has opposite end coil connections, adequate
service clearance equal to unit width is also required on the back side of the unit, in order to ensure easy removal of the
coils.
G.2.2
Supporting surface
Caution
Duct work must be sound insulated and must not be mounted directly on beams, trusses or other critical building parts.
Caution
The surface beneath the unit must be level, horizontal and vibration-free. The surface must be able to withstand the load
of the AHU. Weights of the sections are written in Annex 2.
12
| Instruction for unloading on the site as well as installation and connection
Unit Width
Geniox Model
Width in (mm)
Geniox 10
66.22 (1682)
Geniox 12
74.09 (1882)
Geniox 15
81.96 (2082)
Geniox 20
89.84 (2282)
Geniox 25
97.71 (2482)
Geniox 30
109.52 (2782)
Geniox 35
117.40 (2982)
Geniox 40
125.27 (3182)
Summary of Contents for Geniox 10
Page 2: ...Geniox Air Handling Unit User Manual 3060386...
Page 6: ...Geniox Air Handling Unit User Manual 3060386...
Page 35: ...3060386 Geniox Air Handling Unit User Manual Star up adjustments use and commissioning 29...
Page 61: ...3060386 Geniox Air Handling Unit User Manual ERW maintenance 4 8...
Page 62: ...Geniox Air Handling Unit User Manual 3060386 5 1 Roof curb master tables...
Page 63: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 2...
Page 64: ...Geniox Air Handling Unit User Manual 3060386 5 3 Roof curb master tables...
Page 65: ...3060386 Geniox Air Handling Unit User Manual Roof curb master tables 5 4...
Page 66: ...Systemair NA 8 Rouse Street Tillsonburg ON N4G 5W8 Toll free 800 688 6363...