Setpoint cooling curve
Room setpoint at (32)
26 °C
Room setpoint at (30)
25 °C
Room setpoint at (28)
24 °C
Room setpoint at (26)
23 °C
Offset (-3 up to +3)
0 °C
Setpoint value temperature
26 °C
Offset value
0 °C
Offset value
-1 °C
Setpoint value temperature
25 °C
Room setpoint depending on outdoor temperature
Room setpoint depending on actual outdoor temperature
Start outdoor temp.
Room setpoint at 26 °C
28 °C
30 °C
32 °C
26* °C
23
24
25
26
* Outdoor temp. 26 °C = start point cooling, basic setting
Offset (the temperature curve)
Offset
The curve (see above) will be displayed on the
Actual Value/Setpoint
page. An offset
is possible there.
Example:
The average room temperature setpoint changes from 25 °C to 24 °C with
an outdoor temperature of 30 °C and an offset of -1 °C.
The curve values of the outdoor temperature remain below
Actual setpoint/setpoint
constant also after an offset. The room setpoint changes visibly.
Adjustment range:
-3 °C ... +3 °C
Default setting:
0 °C
Room setpoint as a
fixed value
Room setpoint
After selecting this parameter, the value appears 26°C below the
Actual value/set-
point, Unit, Room setpoint cooling
.
Adjustment range: 22 °C - 28 °C
Factory settings Room setpoint cooling
26 °C
Unit
Status
. tion. tion.
tion. tion. tion.
tion. tion. tion.
Room setpoint cooling
26.0 °C
66
Operation/Control via Internet/App
Genius - V 1.0
Summary of Contents for Combi Unit Genius
Page 4: ...4 Genius V 1 0...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ...Terminal block ventilation module 122 Appendix Genius V 1 0...
Page 123: ......