10.4.2 Hot Water
Hot water
Setpoint
45 °C
Setpoint holiday
30 °C
Fast charge hot water
No
Legionella mode
No
Emergency operation HW
No
Setpoint emergency operation
40 °C
Hot water settings
Setpoint
RECOMMENDATION:
Keep the default settings. This will ensure a high performance
coefficient of the heat pump. The hot water generation starts 1 °C below the setpoint
and stops 2 °C above (adjustable in the service level). When set to
≥
52 °C, the elec-
tric heating rod is switched from 53 °C to reach the setpoint.
Adjustment range:
30 °C ... 55 °C
Default setting:
45 °C
Setpoint holiday
RECOMMENDATION:
Keep the default settings (see
Setpoint
)
Adjustment range:
30 °C ... 40 °C
Default setting:
30 °C
Fast charge hot water
This function ensures hot water comfort in special situations, e.g. for two bath tub
fillings in quick succession. After activating this function, the electric heating rod is
switched on in parallel with the heat pump.
To avoid operating errors, the function is only available during hot water demand. It
automatically turns off after hot water generation.
Settings:
Yes / No
Default setting:
No
Legionella mode
If the legionella mode is activated, the drinking water is once heated to 60 °C in the
night of Sunday to Monday (once a week).
Settings:
Yes / No
Default setting:
No
Emergency operation HW
In case of failure of the heat pump, the user can generate hot water with the electric
heating rod. The function can only be activated manually and during heat pump alarm
to avoid operating errors. Once the fault is removed, the function will be reset.
Settings:
Yes / No
Default setting:
No
Setpoint emergency operation
During the fault, as little electrical power as possible will be consumed at 40 °C .
However, comfort remains active.
Adjustment range:
30 °C ... 50 °C
Default setting:
40 °C
10.4.3 PTC Reheating Elements
PTC
PTC function
Off
Emergency operation
No
Setpoint emergency operation
18 °C
PTC function
In the default setting, the PTC function is deactivated.
Settings:
On / Off
Default setting:
Off
NOTE
Neither an individual room temperature control nor reheating after the PTC start delay time is possible after switching
off the PTC function, see service, settings.
During cooling circuit defrost, the elements will also be activated when switched off.
53
Genius - V 1.0
Operation/Control via Internet/App
Summary of Contents for Combi Unit Genius
Page 4: ...4 Genius V 1 0...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ...Terminal block ventilation module 122 Appendix Genius V 1 0...
Page 123: ......