8.2.1.1 Change Filter
(see „Figure 12: Change filter“)
WARNING
Danger of injury from rotating fans!
Rotating fans can cause very severe injuries.
» Disconnected the unit completely from the power supply before opening!
9
Precondition: The combi unit is disconnected from the power supply.
"
Open the shutter of the ventilation module.
"
Pull out the filters 1, 2 and 3.
"
Insert the new filter.
NOTE
Respect the air flow direction (arrow on the filter).
"
Always check the rotating heat exchanger for contamination (dust) during filter change.
8.2.1.2 Check and Clean Rotating Heat Exchanger
1
Legend
1
Heat exchanger unit
Figure 13: Check and clean rotating heat exchanger
9
Precondition: The combi unit is disconnected from the power supply.
"
Disconnect the two plugs of the rotor unit.
"
Pull out the complete heat exchanger unit.
WARNING
Danger electrical voltage!
Humidity inside the drive motor of the heat exchanger can cause a short circuit.
» Do not expose the drive motor to humidity!
"
Blow the heat exchanger out or rinse it with hot mild suds.
"
Do not use any cleaning detergents.
"
Insert the heat exchanger unit.
"
Connect the two plugs.
"
Close the cover.
"
Connect the Combi Unit Genius to the electrical power supply.
38
Maintenance / Remedying Faults
Genius - V 1.0
Summary of Contents for Combi Unit Genius
Page 4: ...4 Genius V 1 0...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ...Terminal block ventilation module 122 Appendix Genius V 1 0...
Page 123: ......